6 Using the product
14
6.2.
Performing the measurement
WARNING
Risk of injury caused by refrigerant that is at high pressure,
hot, cold, or poisonous!
> Wear safety goggles and protective gloves.
> Before pressurizing the measuring instrument: Always fasten
hot, cold, or poisonous!
> Wear safety goggles and protective gloves.
> Before pressurizing the measuring instrument: Always fasten
the measuring instrument at the suspension device in order to
prevent it from falling (risk of breakage)
prevent it from falling (risk of breakage)
> Check if the refrigerant hoses are intact and connected
correctly before each measurement. Do not use a tool to
connect the hoses. Only tighten the hoses by hand (max.
torque 5.0 Nm/3.7 ft*lb).
connect the hoses. Only tighten the hoses by hand (max.
torque 5.0 Nm/3.7 ft*lb).
> Measures with the occurrence of danger.
Measuring
✓ The steps described in the chapter "Preparing for
measurement" have been completed.
1.
Pressurize the measuring instrument.
2.
Read off readings.
With zeotropic refrigerants, the evaporation temperature
to/Ev is displayed after the complete evaporation/the
condensation temperature tc/Co is displayed after the
complete condensation.
to/Ev is displayed after the complete evaporation/the
condensation temperature tc/Co is displayed after the
complete condensation.
The measured temperature must be assigned to the
superheating or the subcooling side (t
superheating or the subcooling side (t
oh
<--> t
cu
).
Depending on this assignment, t
oh
/T1 or Δt
oh
/SH or t
cu
/T2 or
Δt
cu
/SC is shown depending on the selected display.
- Reading and display illumination flash:
• 1 bar before reaching the critical pressure of the refrigerant,
• upon exceeding the max. permissible pressure of 40 bar.
• upon exceeding the max. permissible pressure of 40 bar.