6 Using the product 
14 
 
6.2. 
Performing the measurement 
 
WARNING
Risk of injury caused by refrigerant that is at high pressure, 
hot, cold, or poisonous! 
>  Wear safety goggles and protective gloves. 
>  Before pressurizing the measuring instrument: Always fasten 
the measuring instrument at the suspension device in order to 
prevent it from falling (risk of breakage) 
>  Check if the refrigerant hoses are intact and connected 
correctly before each measurement. Do not use a tool to 
connect the hoses. Only tighten the hoses by hand (max. 
torque 5.0 Nm/3.7 ft*lb). 
>  Measures with the occurrence of danger. 
 
 
Measuring 
✓   The steps described in the chapter "Preparing for 
measurement" have been completed. 
1.
  Pressurize the measuring instrument. 
2.
  Read off readings. 
 
 
With zeotropic refrigerants, the evaporation temperature 
to/Ev is displayed after the complete evaporation/the 
condensation temperature tc/Co is displayed after the 
complete condensation. 
The measured temperature must be assigned to the 
superheating or the subcooling side (t
oh
 <--> t
cu
). 
Depending on this assignment, t
oh
/T1 or Δt
oh
/SH or t
cu
/T2 or 
Δt
cu
/SC is shown depending on the selected display. 
 
-  Reading and display illumination flash: 
•  1 bar before reaching the critical pressure of the refrigerant, 
•  upon exceeding the max. permissible pressure of 40 bar.