Weigel EQ96K 250/5A 250 A/AC (5A) Assembly dimensions 90 x 90 mm 6.741.302.332 Data Sheet

Product codes
6.741.302.332
Page of 4
Data Sheet
420.D.101.08
K Series
Analog Meters with
Moving-Iron Movement
90
° Dial
Accuracy at Reference Conditions
accuracy class
1.5 according to DIN EN 60 051 - 1
reference conditions
ambient temperature
23
°C
position of use
nominal position 
±1° '
input
rated measuring value
wave form
sinusoidal, distortion factor  5%
frequency
45 ... 65 Hz
others
DIN EN 60 051 - 1
influences
ambient temperature
23
°C±2K
position of use
nominal position 
±5°
frequency
15 ... 100 Hz (voltage)
15 ... 400 Hz (current)
stray magnetic field
0.5 mT
Environmental
climatic suitability
climatic class 3 acc. to VDE/VDI 3540 sheet 2
operating
–10 ... +55
°C
temperature range
storage
–25 ... +65
°C
temperature range
relative humidity
75% annual average, non–condensing
shock resistance
15 g, 11 ms
vibration resistance
2.5 g, 5 ... 55 Hz
Rules and Standards
DIN 43 718
Measurement and control; front - frames and 
frontpanels of measurement and control 
equipment; principal dimensions
DIN 43 802
Line scales and pointers for indicating 
electrical measuring instruments; 
general requirements
DIN 16 257
Nominal positions and position symbols used 
for measuring instruments
DIN EN 60 051
Direct acting indicating analogue electrical 
measuring instruments and their accessories
–1
Part 1: Definitions and general requirements 
common to all parts
–2
Part 2: Special requirements for ammeters 
and voltmeters
–9
Part 9: Recommended test methods
DIN EN 60 529
Enclosure codes by housings (IP - code)
DIN EN 61 010 - 1
Safety requirements for electrical measuring,
control and laboratory equipment
Part 1: General requirements
DIN EN 61 326 - 1
Electrical equipment for measurement, con -
trol and laboratory use – EMC requirements
Part 1: General requirements
DIN IEC 61 554
Panel mounted equipment – 
Electrical measuring instruments – 
Dimensions for panel mounting
VDE/VDI 3540 sheet 2 reliability of measuring and control
equipment (classification of climates)
Options
case
window
non–glaring glass
colour of bezel
gray (similar to RAL 7037)
index marking pointer
red, front adjustable
position of use
on request 15...165
°
marine application
non–certified or
with approbation by ”Germanischer Lloyd”
(except EQ 48 K)
terminal safety protection
full–sized rear cover (except direct–connected ammeters > 25 A),
protective sleeves to go on hexagon studs and  M4 screws with wire
clamps E3
protection against accidental contact (hand and fingers)
acc. to VBG 4 / DIN 57 106, sec. 100
dial
non–calibrated
with dial symbols
blank dial
pencil–marked on initial and end values
scale division
0 ... 100%
and figuring
linear scale division
non–standard captions on request
additional lettering
on request e.g. ”generator”
additional figuring
on request
coloured marks
red, green or blue for important scale values
coloured sector
red, green or blue within scale division
logo on the dial
none or on request
overload scaling
no overload range or
(ammeters)
overload range 5 times rated current