The programme cannot be transferred from IDE to the "C-Control PRO Mini-Station"
• Ensure that the "C-Control PRO Mini-Station" is in BOOT mode and connected to sufficient
power supply. Proceed as follows:
Press the "STOP" button at the "C-Control PRO Mini-Station"
Now the "C-Control PRO" should appear in the output window.
Now the programme can be transferred to the "C-Control PRO" using the "transfer
programme" symbol (green arrow upwards) or the SHIFT+F9 keys.
Caution:
To perform these steps, the Voltcraft USB programmer must first be installed
properly!
The LEDs at the "OUTPUT4" and "OUTPUT5" outputs do not light up when the port has
a HIGH signal.
• The "JP1" and "JP2" jumpers are probably set wrongly or not at all.
• The jumpers must be set in the direction of the relays in normal operation (outputs are used
as output and not for I2C).
EMV impulses, electrostatic discharge = ESD, surge impulse or conductive fail-safety;
the device no longer reacts or has an undefined state.
• Reset it with the "STOP" button..
• Disconnect the device from the power supply and reconnect it.