2.9  Electrical Installation  
WARNING 
 
To ensure the safe operation of the equipment, it must be installed and 
commissioned by qualified personnel in full compliance with the warnings laid 
down in these operating instructions. 
 
Never use high voltage insulation test equipment on cables connected to the 
inverter. 
 
Take particular note of the general and regional installation and safety 
regulations regarding work on dangerous voltage installations (e.g. EN 50178), 
as well as the relevant regulations regarding the correct use of tools and 
personal protective gear. 
 
The mains input, DC and motor terminals, can carry dangerous voltages even if 
the inverter is inoperative; wait 5 minutes to allow the unit to discharge after 
switching off before carrying out any installation work. 
 
The inverters can be installed in a side-by-side configuration with a minimum 
distance as shown in Figure 2-4 on page 22. 
CAUTION 
The control, power supply and motor leads must be laid separately. Do not feed 
them through the same cable conduit/trunking.
 
2.9.1 General 
WARNING 
The inverter must always be grounded
. If the inverter is not grounded correctly, 
extremely dangerous conditions may arise within the inverter, which could prove 
potentially fatal. This also applies to ungrounded IT supplies 
Operation with ungrounded (IT) supplies 
 
Filtered inverters CANNOT be used on ungrounded supplies. 
 
FSA unfiltered inverter can be used on ungrounded supplies. 
If an output phase is shorted to ground, the inverter may trip with F0001 
(overcurrent). 
 
FSB and FSC can be used on ungrounded supplies, but it is necessary to cut 
the ‘Y’ capacitor link as described in Removal of ‘Y’ Capacitor Link on page 71. 
If an output phase is shorted to ground, the inverter may trip with F0001 
(overcurrent).