04/2003 Commissioning 
SINAMICS G110    Operating Instructions 
 
6SL3298-0AA11-0BP0 
31
 
3 Commissioning 
This section describes the different methods of how to commission and run the 
SINAMICS G110 inverter. A prerequisite is that the mechanical and electrical 
installation has been completed as described in Section 2, starting on page 17 of 
these Operating Instructions. 
 
WARNING 
 
SINAMICS G110 inverters operate at high voltages. 
 
When operating electrical devices, it is impossible to avoid applying hazardous 
voltages to certain parts of the equipment. 
 
Emergency Stop facilities according to EN 60204 IEC 204 (VDE 0113) must 
remain operative in all operating modes of the control equipment. Any 
disengagement of the Emergency Stop facility must not lead to uncontrolled or 
undefined restart. 
 
Wherever faults occurring in the control equipment can lead to substantial 
material damage or even grievous bodily injury (i.e. potentially dangerous 
faults), additional external precautions must be taken or facilities provided to 
ensure or enforce safe operation, even when a fault occurs (e.g. independent 
limit switches, mechanical interlocks, etc.). 
 
Certain parameter settings may cause the inverter to restart automatically after 
an input power failure. 
 
Motor parameters must be accurately configured for motor overload protection 
to operate correctly above 5 Hz. 
 
This equipment is capable of providing internal motor overload protection in 
accordance with UL508C. Refer to P0610 and P0335, I
2
t is ON by default.  
 
This equipment is suitable for use in a circuit capable of delivering not more 
than 10,000 symmetrical amperes (rms), for a maximum voltage of 230 V, when 
protected by an H or K type fuse, a circuit breaker or self-protected combination 
motor controller. 
 
This equipment must not be used as an ‘emergency stop mechanism’ (see EN 
60204, 9.2.5.4) 
CAUTION 
Only qualified personnel may enter settings in the control panels. Particular 
attention must be paid to safety precautions and warnings at all times. 
NOTES 
 
The inverter does not have a main power switch and is live when the mains 
supply is connected. It waits, with the output disabled, until the RUN button is 
pressed or for the presence of a digital ON signal at terminal 3. 
 
The inverter is designed to use control input signals to start and stop the motor.