Novatek SINGLE-PHASE VOLTAGE RELAY RN-113 RN-113 Data Sheet

Product codes
RN-113
Page of 5
- 5 -
If  RN-113 was initially reenergized or the power load was  OFF due to the wrong voltage parameters – then after
correct voltage appear on the input terminals and after the time delay Ton contacts  1,3 will open and contacts 2,3 will
close. 
If input voltage get lower than minimal voltage threshold for more than  12 sec RN-113 becomes to  Alarm mode  –
contacts 1,3 close and contacts 2,3 open and thus the power load should be turned OFF. 
If input voltage gets 50V lower than the minimal voltage tripping threshold – RN-113 turns OFF the power load within
0,2 sec (accelerated tripping time). After the recovery of the voltage parameters to the value of hysteresis (4-5V) – RN-113
turns ON the power load with the user adjusted time delay T
on
.
4.5 Maximal voltage protection relay
Power load (contactor coil) should be connected to the output terminals 1, 3.
When normal voltage applied to the input terminals of RN-113 – the state of the output relay doesn’t change so the
RN-113 stay in the “cold” state: contacts 1,3 are closed and contacts 2,3 are opened. 
If input voltage gets higher than the maximal tripping voltage threshold for more than 1 sec or accelerated tripping
time of 0,2 sec is applied if the voltage is 30V higher than the maximal tripping threshold – then the RN-113 comes to
Alarm mode – contacts 1, 3 open and contacts 2,3 close. 
When voltage level decrease lower than the maximal tripping voltage threshold to the hysteresis value 
4-5V – RN-113 turns ON the power load with the user adjusted time delay T
on
.
4.6 Minimal/Maximal voltage protection relay
Power load (contactor coil) should be connected to the output terminals 2,3.
If  RN-113 was initially reenergized or the power load was  OFF due to the wrong voltage parameters – then after
correct voltage appear on the input terminals and after the time delay Ton contacts  1,3 will open and contacts 2,3 will
close. 
If input voltage get lower than minimal voltage threshold for more than  12 sec  RN-113 becomes to  Alarm mode  –
contacts 1,3 close and contacts 2,3 open and thus the power load should be turned OFF. 
If input voltage gets 50V lower than the minimal voltage tripping threshold – RN-113 turns OFF the power load within
0,2 sec (accelerated tripping time). After the recovery of the voltage parameters to the value of hysteresis (4-5V) – RN-113
turns ON the power load with the user adjusted time delay T
on
.
If input voltage gets higher than the maximal tripping voltage threshold for more than 1 sec or accelerated tripping
time of 0,2 sec is applied if the voltage is 30V higher than the maximal tripping threshold – then the RN-113 comes to
Alarm mode – contacts 1, 3 open and contacts 2,3 close. 
When voltage level decrease lower than the maximal tripping voltage threshold to the hysteresis value 4-5V – RN-113
turns ON the power load with the user adjusted time delay T
on
.
4.7 Turn ON time delay relay
In this mode voltage parameters are not controlled and RN-113 will turn ON the power load with the user preset time
delay (T
on
) if the input voltage parameters are within the operation voltage range.
Power load (contactor coil) should be connected to the output terminals 2,3.
If the input voltage is more than 160V  RN-113  will turn  ON the power load after the delay time will finish. If the
voltage will get lower than 152V RN-113 will go to Alarm mode – contacts 1,3 close and contacts 2,3 open and thus the
power load should be turned OFF.
5. WARRANTY AND CLAIMS CONDITIONS
Novatek-Electro Ltd. company warrants a trouble-free operation of the  RN-113 device within three years from the
date of sale, on condition that following terms are provided:
-- the proper connection;
-- the safety of the inspection quality control department seal;
-- the integrity  of the case,  no traces of opening,  cracks, spalls etc.
6 TRANSPORTATION
Transportation of RN-113 in package may be effected by any type of transport according to the transportation rules
and regulations valid for such mode transportation.
During transportation, shipping and storing in a warehouse  RN-113
 
 must be protected form blows, shocks and
moisture.
7 QUALITY ASSURANCE NOTES 
The RN-113  multifunctional time delay relay has been manufactured and accepted in conformity with the
requirements of current technical documentation, and is approved fit for operation.
 
NOVATEK-ELECTRO
                                                                                            
RN-113