2. Description
The MCR-S-…-DCI, active current transducers convert direct, alternating and distorted currents from 0… 
0.2 A to 0…11 A (MCR-S-1-5-...-DCI) and from 0…9.5 A to 0…55 A (MCR-S-10-50-…-DCI) to analog 
standard signals.
On the output side, the analog standard signals of 0(4)…20 mA, 0(2)…10 V, ±10 V, 0(1)…5 V, ±5 V with 
simple (e.g. 0…10 V) and inverse (e.g. 10…0 V) signal flow direction can be used.
An option for the current transducers with threshold output (MCR-S-…-SW-DCI) is a PNP transistor swit-
ching output (80 mA) and a relay switching output (2 A).
2.1. Method of operation
Connecting to the input terminal blocks (MCR-S-1-5-…-DCI), or passing the live conductor through the 
current transducer (MCR-S-10-50-…-DCI) evokes a magnetic flow in the annular strip-wound core. 
The density of magnetic flow is measured with the aid of a Hall sensor and converted proportionally from 
the input current to a voltage (Hall voltage). A downstream true r.m.s. converter enables DC, AC and 
distorted currents to be measured. The signal is amplified for further conditioning and made available at 
the output as a proportional analog signal.
2.2. Versions
This package insert is valid for the following types of current transducers:
3. Block diagram
Type
Order No.
Measuring range
Threshold value function
MCR-S-1-5-UI-DCI
2814634
0…0,2 A 
to 
0…11 A
no
1
)
MCR-S-1-5-UI-DCI-NC
2814715
no
2
)
MCR-S-1-5-UI-SW-DCI
2814650
yes
1
)
MCR-S-1-5-UI-SW-DCI-NC
2814731
yes
2
)
MCR-S-10-50-UI-DCI
2814647
0…9,5 A 
to 
0…55 A
no
1
)
MCR-S-10-50-UI-DCI-NC
2814728
no
2
)
MCR-S-10-50-UI-SW-DCI
2814663
yes
1
)
MCR-S-10-50-UI-SW-DCI-NC
2814744
yes
2
)
1)
 Configuration is done using the order key following user specifications.
2)
 The module is supplied in the standard configuration.
OUT
µC
ADC
DAC
DAC
OUT
U
SP
AN
9
OUT U
GND 2
GND 2
10
11
12
OUT I
Po
wer
=
12
11
14
1
2
3
4
NC
ZE
R
O
TIM
E
24VDC
GND 1
SW
13
14
15
GND 1
16
IN
I
SET
POINT
OUT
SP
AN
12
10A
11
5A
14
1A
1
5
2
6
3
7
4
8
NC
ZE
R
O
TIM
E
IN
SET
MCR-S-1-5-...