UR3274U - User manual
  
7.5 
Soft Start
To reach the setpoint the controller can follow a gradient 
expressed in units (e.g. degree/hour).
Enter this gradient on parameter 51 
Grad.
 with the chosen 
units/hour; only on subsequent activation the controller 
uses soft start function.
Automatic/manual tuning cannot be enabled if the Soft start 
is active.
7.6 
Automatic/Manual Regulation for % 
Output Control
This function allows to select automatic functioning or ma-
nual command of the output percentage.
Parameter 49 
Au.ma.
, can select two methods.
•  First selection 
en.
 
  pressing the 
FNC
 key display 1 shows 
p.---
, while display 2 
shows 
Auto
.
  Press the 
 key to select 
man.
 mode; it is now possible, to 
change the output percentage using the keys 
 and 
. To return to automatic mode, using the same procedure, 
select 
auto
 on display 2: 
M
 led switches off and functio-
ning returns to automatic mode.
•  Second selection
en.st.
 
  same functioning, but with two important variants:
•  If there is a temporary power failure or after switch-off,
manual functioning as well as the previous output 
percentage value will be maintained at restarting.
•  If the sensor breaks during automatic functioning, con-
troller moves to manual mode while maintaining the