Panasonic AKT4111100J Temperature Controller KT4 AKT4111100J Data Sheet

Product codes
AKT4111100J
Page of 11
 
KT(AKT4,7,8,9)
 
5
 
Breakdown vibration
10 to 55Hz (0.75mm) to each direction (120ms sweep) for 10min.
Malfunction shock
X, Y & Z each direction for 5 times 10G
Breakdown shock
Same as above, but 30G
Ambient temperature
0 to 50°C
Ambient humidity
35 to 85%RH (No condensation)
Mass
Approx. 130g
Approx. 240g
Approx. 370g
Approx. 150g
Waterproof
IP66 (applicable only to the front panel subject to rubber gasket employed)
None
Display character height
PV: 10.2mm
SV: 8.8mm
PV: 11.2mm
SV: 11.2mm
PV: 18mm
SV: 13.2mm
PV: 7.4mm
SV: 7.4mm
Options
Alarm output 2
The same as the one of Alarm output 1
None
Heating/Cooling  
control
Non contact relay
0.3A 250V AC (Resistive load)
   • Relay contact: 1a 250V AC 3A (Resistive load),
     250V AC 1A (Inductive load cosø=0.4),
     Electric life: 100,000 times
   • Non-contact voltage: 12 V DC Max. 40mA
     (Short-circuit protected)
   • DC current: 4 to 20mA DC  Load resistance: Max. 550
 
Ω
 
None
Heater burn-out alarm 
output
Heater rated current must be selected from 5A, 10A, 20A and 50A.
Setting accuracy:  Within 5% of heater rated current
Relay contact 1a 250V AC 3A (Resistive load), Electric life: 100,000 times
Open collector, Control 
capacity: 24V DC 0.1A (Max.)
Display
Specifications
KT4
KT8
KT9
KT7
+2
0
 
 
 COMMUNICATION FUNCTION OVERVIEW
 
Note) That main setting No. 2 will not be possible on the KT8 and KT9 when the communications functions is added.
Item
Specification
Communication type
Half-duplex
Communication speed
Select 2400, 4800, 9600, or 19200 bps using key operation.
Synchronization type
Asynchronous
Protocol
Modbus
Coding
ASCII
Error correcting
Command re-send
Error detection
Parity check, check sum
Data structure
Start bit: 1
Data bit: 7
Parity: Even parity
Stop bit: 1
Interface
RS485 compliant
No. of nodes
31
Maximum cable length
1,000 m (cable resistance must be within 50
 
Ω
 
)