Panasonic AKT4111100J Temperature Controller KT4 AKT4111100J Data Sheet

Product codes
AKT4111100J
Page of 11
 
KT(AKT4,7,8,9)
 
6
  
 
 
 
 Here are described the basic operating procedures (In case of KT4).
Operating Procedure
  Step 1 - Initialization
In auxiliary function setup mode 2, 
select entry type, alarm behavior, 
control behavior, etc.
  Step 2 - Calibration
In ancillary setup mode, set the PID 
and alarm values.
  Step 3 - Lock Setup
In auxiliary function setup mode 1, set 
the setting lock, SV max, and SV min. 
(If Step 3 is not necessary, proceed to 
Step 4.)
  Step 4 - Operation Setup
In main setup mode, set the SV (target 
value).
Sample configuration:
Input sensor:
K thermocouple (–200 to 1,370
°
C)
Control method:
PID
Alarm behavior:
Max alarm (deviation setting)
Control behavior: Inverse (heat)
A1 setting:
50
°
122
°
F
SV (target value): 150
°
302
°
F
AT setting:
Run AT
To set up the system as shown above:
1) In Step 1 - Initialization, set the necessary values in auxiliary function 
setup mode 2.
2) In Step 2 - Calibration, set the necessary values in ancillary setup mode.
3) In Step 4 - Operation Setup, set the SV (target) value in main setup 
mode, and begin control.
4)  In ancillary setup mode, under AT Setup/Auto Reset Setup, set AT, and 
press the MODE key to begin AT.
See the flowchart below for the operation sequence.
Press         for about 1 second.
Press         .
Press         while holding down         .
[Main Setup Mode]
[Ancillary Setup Mode]
Press          for about 3 seconds while holding down         .
[Auxiliary Function Setup Mode 1]
Press         .
PV/SV Display
Control output off function or
auto/manual control function
Return to PV/SV Display
SV (target value setting)
AT Setting/
Auto Reset Setting
OUT1
Proportional Band
Setting Lock Selection
SV Max Setting
Sensor Calibration Setting
SV Min Setting
Select Communication Protocol
Select Communication Speed
Set Device Number
Select Parity
Select Stop Bit
Setting
About the         Key
The symbol [           ] means 
press the         key to save
the setting, and proceed to
the next setup item.
Output Operation
Volume Display
Press         for about 3 seconds.
• If AT is cancelled, PID returns to the value it 
had before AT was run.
• Auto reset is released after about 4 minutes.
• Set the value using the          and          keys.
• Set 0, 0.0 for ON/OFF operation.
• Set the value using the          and          keys.
• Set the value using the          and          keys.
• Select the communication protocol using the 
            and          keys.
• Set the device number using the          and
            keys.
• Select the parity using the          and      
keys.
• Select the stop bit using the          and
keys.
• Select the communication speed using the
            and          keys.
• Set the value using the          and          keys.
• Make a selection using the          and       
keys.
• AT and auto reset will not function if lock 1/2 
specified.
OUT2
Proportional Band
Integral Time Setting
Derivative Time
Setting
OUT1 Proportional
Frequency Setting
OUT2 Proportional
Frequency Setting
A1 Setting
A2 Setting
Heater Cutoff Alarm
ARW Setting
• Set the value using the          and          keys.
• Displayed if heating/cooling control (OUT2) 
is added.
• Set the value using the          and          keys.
• Set to 0 for PD operation, enabling auto 
reset.
• Set the value using the          and          keys.
• Derivative operation will not function if set to 
0.
• Set the value using the          and          keys.
• Displayed during PID operation.
• Set the value using the          and          keys.
• Not displayed when OUT1 is in ON/OFF 
operation, or when output is direct current.
• Set the value using the          and          keys.
• Not displayed when OUT2 is in ON/OFF 
operation.
• Set the value using the          and          keys.
• Not displayed when [A1 Operation Selection] 
is [             ].
• Set the value using the          and          keys.
• Not displayed when [A2 Operation Selection] 
is [             ].
• Set the value using the          and          keys.
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Return to PV/SV Display
Return to PV/SV Display
Notes 1. Sample Alarm 1 (A1) Setup Procedure (Settings marked 
1
2
3
4
, and 
5
 on flowchart).
1
: Under [A1 Operation Selection], select the alarm 
operation. (If a value other than [          ] is selected, 
items (2) to (5) are displayed. Set them as 
necessary.)
2
: Under [A1 Operation Energized/Non-energized 
Selection], select Alarm 1 contact output ON 
(energized:         ), OFF (non-energized:         ).
3
: Under [A1 Operation Gap Setting], set the Alarm 1 
operation gap.
4
: Set [A1 Operation Delay Timer Setting] (After input 
enters alarm operation range, the alarm behavior will 
take effect if the setup times out.
5
: Under [A1 Setting], set the A1 output operation point.
2. See the user’s manual for information on KT 7, 8, and 9.
3. See the user’s manual for details on factory settings.
Selection
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting