Running Projects and Controlling the nanoLC
2373_en_B
PHOENIX CONTACT
6-7
6.8
Clearing the Memory Module
To clear a project from the nanoLC Memory Module, follow these steps:
1.
Attach the nanoLC Memory Module to the PC using the configured USB port (see 
“Specifying the PC Connection” on page 6-3) and a standard A-B USB cable.
2.
Select “nanoLC... Memory Module... Clear Project” to clear the project from the 
memory module. 
6.9
Running a Project
To run a project on the nanoLC from nanoNavigator, follow these steps:
1.
If nanoNavigator isn’t currently connected to the nanoLC, follow the steps in 
2.
Select the “nanoLC... Run nanoLC!” menu to begin or stop execution. The “Run 
nanoLC!” menu always begins execution at the top of each flow chart. Data Items that 
are not retentive have their values reset to their initial values.
6.10
Stopping a Running Project
The project will continue to run all flow charts and I/O read/writes until halted. To stop the 
project, connect to the controller (see “Connecting to the nanoLC” on page 6-5), and then 
select the “nanoLC... Stop nanoLC!” menu.
6.11
Set nanoLC Password
To set the password on the nanoLC from nanoNavigator, follow these steps:
1.
If nanoNavigator isn’t currently connected to the nanoLC, follow the steps in 
2.
Select the “nanoLC... Set Password” menu. 
WARNING:
Any machine or process on the I/O network under Runtime control will cease operation. 
This can lead to dangerous, even life-threatening situations in some applications. A 
confirmation box indicates that the running project is about to be stopped.