Axioline bus coupler for PROFINET (including bus base module and connector)
Product Description
The bus coupler links a PROFINET network with the Axioline system.Up to 63 Axioline devices can be connected at any point to an
existing PROFINET system using the bus coupler.For startup tests you can put the Axioline station into operation independent of the
higher-level network either using the service interface or an Ethernet port at the bus coupler.  
Product Features
 Up to 63 additional Axioline devices can be connected
 Firmware can be updated
 Minimum cycle time of PROFINET for RT is 250 μs
 Diagnostic and status indicators
 Runtime in bus coupler is negligible (almost 0 µs)
 PROFINET RT
 Typical cycle time of the Axioline system bus is around 10 μs
 2 RJ45 connections (with integrated switch)
 Module replacement without software
  
Key commercial data
package_quantity
1
GTIN
4046356501613
Technical data
Dimensions
Width
40 mm
Height
123.6 mm
Depth
75 mm
Note on dimensions
The depth is valid when a TH 35-7.5 DIN rail is used (according to
EN 60715).
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (according to DIN EN 61131-2)