5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
231
 
●  Multiple function switch: Ta 
●  Stopwatch: AQ 
●  Analog filter: AQ 
●  Average value: AQ 
●  Max/Min: AQ 
●  Threshold trigger: Fre 
You select the required function by the block number. 
Timing diagram 
 
Description of the function 
With the 0 to 1 transition at input En, a random time (on-delay time) between 0 s and T
H
 is 
set and triggered. If the status at input En is 1 for at least the duration of the on-delay, the 
output is set to 1 when this on-delay time has expired. 
The time is reset if the status at input En is reset to 0 before the on-delay time has expired. 
When input En is reset 0, a random time (off-delay time) between 0 s and T
L
 is set and 
triggered. 
If the status at input En is 0 at least for the duration of the off-delay time, the output Q is 
reset to 0 when the off-delay time has expired. 
The time is reset if the status at input En returns to 1 before the on-delay time has expired. 
Special functions (Page 212)