Phoenix Contact Inline function terminal IB IL TEMP 2 RTD-PAC 2861328 2861328 Data Sheet

Product codes
2861328
Page of 7
Nov 13, 2013    1 / 7
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Inline analog input terminal, complete with accessories (connector plug and labeling field), 2 inputs,
RTD (resistance temperature detector), 2-, 3-, 4-wire connection technology
Product Description
Using these analog input terminals, it is possible to measure signals from conventional thermocouples and resistance thermometers.The
terminals are configured for connection to various types of sensors. The user can configure the different sensor characteristic curves
himself via process data. It is thus possible to attain the best possible adaptations in very different applications.The Inline terminals can
be labeled using hinged labeling fields. The fields have insert cards that can be labeled individually to suit the application. Additionally,
there is the proven ZBFM-6... Zack strip for labeling the terminal points.  
Product Features
 Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
 Measured value acquisition with 16-bit resolution
 Channel scout for optical channel identification
 Connection of sensors in 2, 3, and 4-wire technology
Key commercial data
package_quantity
1
GTIN
4017918894269
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
12.2 mm
Height
136.8 mm
Depth
71.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20