Phoenix Contact Safety module IB IL 24 LPSDO 8-PAC 2916024 2916024 Data Sheet

Product codes
2916024
Page of 6
Nov 13, 2013    1 / 6
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has
four safe digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel
occupancy
Product Description
The safety module is an output module from the Inline product range and is used in a SafetyBridge system. The safety module can
be used as a part of an Inline station at any point within an INTERBUS, PROFINET or PROFIBUS system. The transmission speed
of the safety module can be set to 500 kbaud or 2 Mbaud using a switch. Only one transmission speed must be used uniformly
within a station. The module has four safe digital outputs with two-channel occupancy or eight safe digital outputs with single-channel
occupancy. In the SafetyBridge system, you can achieve the following safety integrity by using this safety module depending on the
installation and parameterization:– up to category 4 according to EN 954-1 standard,– up to SIL 3 according to EN 61508 standard,– up
to SIL CL 3 according to EN 62061 standard,– up to PL e according to EN ISO 13849-1 standard.  
Product Features
 Generation and monitoring of the SafetyBridge protocol
 Processing of the parameterized safety logic
Key commercial data
package_quantity
1
GTIN
4046356479110
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air
humidity within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air
humidity within the permitted temperature range.)
Air pressure (operation)
80 hPa ... 108 kPa (up to 2000 m above sea level)