Phoenix Contact I/O module AXL DI 32/1 2688035 2688035 Data Sheet

Product codes
2688035
Page of 7
Nov 14, 2013    1 / 7
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Axioline digital input module, 32 inputs, 24 V DC, single-wire connection method (including bus base
module and connectors)
Product Description
The module is designed for use within an Axioline station.It is used to acquire digital signals.The filter times of the inputs can be
adjusted to increase noise immunity.Filter times of 100 μs enable the user to implement a counter function with a maximum input
frequency of 5 kHz in the application.  
Product Features
 32 digital inputs according to EN 61131-2 type 1 and type 3
 24 V DC, 2.4 mA
 Connection of sensors in single-wire technology
 Minimum update time of < 100 μs, bus synchronous
 Filter times can be adjusted in three increments: < 100 µs, 1000 µs or 3000 µs
 Maximum input frequency: 5 kHz
 Device rating plate stored
 Diagnostic and status indicators
Key commercial data
package_quantity
1
GTIN
4046356501590
Technical data
Dimensions
Width
53.6 mm
Height
126.1 mm
Depth
54 mm
Note on dimensions
The depth is valid when a TH 35-7.5 DIN rail is used (according to
EN 60715).
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)