Chapter 6  
Response message format for function code 01:
Example: Coils number 2 and 7 are on, all others are off.
         01 01 01 42
In the response the status of coils 1 to 8 is shown as the byte value 42 hex, 
equal to 0100 0010 binary.
Function Code 02 
The function code 02 is used to read the discrete inputs ON/OFF status of 
ADAM-6000 in a binary data format.
Request message format for function code 02:
Example: Read coil number 1 to 8 (address number 00001 to 00008) from 
ADAM-6000 modules
         01 02  00 01 00 08
Response message format for function code 02:
Example: input number 2 and 3 are on, all others are off.
         01 02 01 60
In the response the status of input 1 to 8 is shown as the byte value 60 
hex, equal to 0110 0000 binary.
                                               Command Body
Station 
Address
Function 
Code
Byte Count
Data
Data
                                                 Command Body
Station 
Address
Function 
Code
Start 
Address 
High Byte
Start 
Address 
Low Byte
Requested 
Number of Input 
High Byte
Requested 
Number  of 
Input Low Byte
                                            Command Body
Station 
Address
Function 
Code
Byte Count
Data
Data