Note: When your output destination is not Local, meaning there will be 
communication between the specific ADAM-6000 module to its target 
device, remember to use Ethernet switch to connect the ADAM-6000 
module with its target device. Do not use an Ethernet hub. This can pre-
vent data packet collision. 
After you decide the target device, then you can choose the output action 
by the Operation Type combo box. The default setting is NoOperation
meaning there is no output action. You can choose analog output (AO), 
digital output (DO), counter channel setting (DI_counter), pulse output 
(DO_Pulse), local timer (Timer), local or remote internal flag (Aux-
Flag
), remote message output (RemoteMessage) and local internal 
counter setting (Counter) as the output action. 
After you have chosen the target device and output action, you can click 
the Verify button to check if the target device exists and supports GCL 
feature to execute the output action. (If you choose NoOperation as out-
put action, it will not check.) After you choose the appropriate output 
action and complete all related setting, click the OK button. That Output 
stage icon will change its pattern to present the current condition. We will 
describe each output action in more detail below. 
Analog Output (AO)
Below are the steps to configure analog output:
1.
Choose correct model name by the Target module combo box in 
the Operation area. If the Destination is Local, you don't need to 
choose the model name. 
2.
Choose the appropriate output range by the TargetRange combo.
3.
Define which channel is responsible to generate output signal on 
the target device by the Channel combo box. 
4.
Define what value is generated by the Value text box. (The unit of 
the value depends on the range in the TargetRange combo box.)
5.
Click the OK button to complete the configuration. 
Note: You can see the action description by the Action text box. When the 
logic result value passed from Execution stage is logic True, the selected 
analog output channel will generate the new value you defined. When the 
logic result value passed from Execution stage is logic False, the selected 
analog output channel will not change its output value.