Lappkabel 30017798, Alarm Cable, , Red Sheath 30017798 Data Sheet

Product codes
30017798
Page of 2
U.I. Lapp
GmbH
DATASHEET
J-H(ST)H...BD Fire Alarm Cable
30017798
14.11.2013
 
 
PN 0486/0_03.0
Halogen-free installation cable in accordance with DIN VDE 0815 with red outer sheath
Used to meet enhanced fire protection requirements concerning protection of people and high-value property
Does not emit any toxic or corrosive gases in the event of fire and resists the spread of fire
Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency,
electromagnetic fields
Decoupling of circuits by means of twisted-pair (TP) design (crosstalk effects)
J-H(ST)H...BD Fire Alarm Cable is marked with the phrase “Fire alarm cable” at regular intervals on the sheath. It is therefore
used especially for installation in fire alarm systems.
Flame-retardant
Halogen-free
Interference signals
Application range
This halogen-free, flame-retardant installation cable with static screen is used for telephone, data and signal transmission in
subscriber stations and private branch exchange construction for telephone systems
For fixed installation on and under plaster, in dry and damp rooms
Design
Solid bare copper conductor
Core insulation made of special halogen-free compound
Cores twisted into star quads, 5 star quads are twisted into a bundle, bundles stranded in layers
Foil wrapping, static screening made of aluminium-laminated plastic film with copper drain wire
Outer sheath made of special halogen-free compoundOuter sheath colour: flame red (RAL 3000)
Norm references / Approvals
Based on DIN VDE 0815
Product features
Flame-retardant according IEC 60332-1-2
No flame-propagation according to IEC 60332-3-24 respectively IEC 60332-3-25 (Flame spread on vertical cable or wire
bundle)
Halogen-free according to EN 50267-2-1/-2
Remark
Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon
request.
Copper price basis: EUR 100/100kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related
surcharges.
Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum