Lappkabel 3022673, Cable, , Black Sheath 3022673 Data Sheet

Product codes
3022673
Page of 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
 
 
NSHXAFö 1.8/3 kV
 
 
DB3022673EN                    
valid from: 2010-08-20
 
 
 
Originator: T. Merker / PDC
 
Document: 
DB3022673EN 
page 1 of 1 
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.  
PD 0019/2.1_11.09EN 
MAKE-UP TYPE 
NSHXAFö 1,8/3 kV 
 
CERTIFICATION 
NSHXAFö 1,8/3 kV ◄VDE► (arrowheads can also be blank) according to VDE 0250-606 
 
APPLICATION 
(VDE 0298-3) 
-
 
Railway vehicles 
-
 
Omnibuses 
-
 
Switching stations (short-circuit-proof up to 1000 V) 
-
 
Power distributors (short-circuit-proof up to 1000 V) 
-
 
No direct laying in the ground 
-
 
Lead-through through fire separation (e.g. sand cups) is permissible and doesn’t represent laying in ground normatively 
-
 
Removal of tensile load, thrust, torsion and bend is necessary in case of connection to non-stationary equipment 
-
 
No appropriateness for protection class II 
-
 
In ducts, tubes, pipes, conduits 
-
 
In closed installation channels 
-
 
Machine or tool wiring 
-
 
Connection of movable parts 
-
 
Bundled 
-
 
Potentially for the protection of life & material assets in case of fire due to halogen-free materials, at the applications mentioned 
-
 
Maximum laying tensile strength 
At stationary installation 
 
50 N per mm² of nominal conductor cross section 
At movable equipment 
 
15 N per mm² of nominal conductor cross section 
 
PERMISSIBLE VOLTAGES 
Rated, core-to-ground (PE) (U
0
 
1.8 kV AC/2.7 kV DC 
Rated, core (not PE)-to-core (not PE) (U) 
3.0 kV AC/4.5 kV DC 
Operated, core-to-ground (PE) (U
0
 
2.1 kV AC/2.7 kV DC 
Operated, core (not PE)-to-core (not PE) (U) 
3.6 kV AC/5.4 kV DC 
 
MAKE-UP 
(DIN VDE 0250-606) 
Conductor 
 
 
 
Copper 
Conductor class 
 
 
 
Fine-wired/Class 5 according to IEC 60228/EN 60228/VDE 0295 
Conductor quantity  
 
 
Single-conductor/1 x … 
Cross sections in mm² 
 
 
1.5 to 300 
Insulation  
 
 
 
Extruded rubber compound 3GI3 acc. to DIN VDE 0250-606.4.3 & DIN VDE 0207-20 
 
 
 
 
 
Wall thickness in line with DIN VDE 0250-606, table 4, column 4 
Outer coating 
 
 
 
Halogen-free polymer compound HM3 acc. DIN VDE 0250-606.4.5 & DIN VDE 0207-24 
 
 
 
 
 
Wall thickness in compliance with DIN VDE 0250-606, table 4, column 5 
Outer cable diameter 
 
 
DIN VDE 0250-606, table 4, column 6 
Standard colour of the outer coating   
Black (other colours on request) 
 
ELECTRICAL PROPERTIES AT +20 °C 
Rated voltage U
0
/U 
 
 
1.8/3 kV AC 
Test voltage 
 
 
 
6000 V AC 
 
MECHANICAL, CHEMICAL AND THERMAL PROPERTIES 
Category temperature in each situation 
At the conductor, during operation 
+90 °C 
 
 
 
 
 
At the surface, fix laying 
 
-40 °C to +90 °C 
 
 
 
 
 
At the surface, during laying   
-25 °C to +70 °C 
Minimum bending radii 
 
 
Installed fixedly 
 
 
6 x OD* 
 
 
 
 
 
Moved freely 
 
 
10 x OD* 
 
 
 
 
 
At insertion 
 
 
10 x OD* 
 
 
 
 
 
Drum operation (enforced guidance) 
12 x OD* 
 
 
 
 
 
Cable roller assemblies (enf. guidance) 10 x OD* 
 
 
 
 
 
Roll direction change 
 
15 x OD* 
Halogen-free 
 
 
 
DIN VDE 0250-606 -2.2 and -4.7 
Fire load values 
 
 
 
DIN VDE 0250-606, table 4, column 7 
European low voltage directive 
 
Not compliant with the low voltage directive (CE) due to the rated voltage above 1 kV 
 
*OD = Outer cable diameter