Fanox 11403 P19 Pump Protection Relay 11403 Data Sheet

Product codes
11403
Page of 1
15
Models
Code
Relay type
ODP
12540
P
MODELS
P 19
P 44
P 90
Adjustment range
 Motor  400 V
50/60 Hz
I
B
 (A)
7 - 19,6
19 - 44,2
40 - 90,4
CV
4 - 10
12,5 -27,5
27,5 - 55
kW
3 - 7,5
9,2 - 20
20 - 40
Code
  
according to the 
relay voltage supply 
(+15% -10%) 
ac: 50/60 Hz
230 Vac 
single phase
11403
11423
11443
115 Vac
single phase
11402
11422
11442
24 Vac, dc single phase
11400
11420
11440
For 
,
N
 
of the motor below the minimum setting 
,
B
Pass the cables several times (n) through the holes in the relay
 
,
B
 = n x 
,
N
For 
,
N
 
of the motor above the maximum setting 
,
B
Use 3 CT .../5 and the relay P 19
External display module (optional)
ODP
CHARACTERISTICS
Thermal memory / Overload trip
Yes / From 1,1 x 
,
B
Maximum motor nominal voltage
1000 Vac
Trip classes (IEC 947-4-1)
5 - 10 - 15
Phase sequence protection
Yes
Phase imbalance protection
Over 40%. Tripping time < 3s
Undercurrent protection adjustable / Trip delay
From 0,5 to 0,9 x 
,
B
 . Operative from 0,3 x 
,
/ 3s
Reset mode for protection against dry running
 manual, remote and automatic. More info in page 28
Reset mode for other protection functions
Manual, remote and automatic (every 15 minutes)
Signalling LED’s
4 LED’s: ON + 
 + 
 +   
Output contacts
1 relay with 1 NO + 1 NC
Switching power 
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
Terminals: Max. section / screw torque
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
Power consumption
2,5 VA
Protection degree / weight / mounting
IP20 / 0,5 kg / DIN rail 
Storage temperature
-30°C +70°C
Operation temperature / max. altitude
-15°C +60°C / 1000m; -15°C +50°C / 3000m
Normas
IEC 255, IEC 947, IEC 801, EN 50081-2
    
DIMENSIONS P RELAY (mm)
DIMENSIONS ODP MODULE (mm)
WIRING DIAGRAM (mm)
P
  Overload
Undercurrent
  Phase imbalance 
or phase loss
Phase sequence
PROTECTION
FUNCTIONS
ODP
Ø 22,5
Ø 30,0
11,3
20,0
1 = 2 m
L3
L2
L1
13
M
14
U1 V1 W1
A2
N
K1
A1
L1
13-K1
14-K1
Tripped
or Us=0
Normal
98
98
98
96
A2
A1
95
97
97
97
96
96
95
95
80
35,4
38
45
99
94
5
78
17,5
12
12
17,5
50
Settings and curves,see pages 24 to 29.
P
P
•  Eliminates need for level sensors to detect dry running.
•  For 3-phase motors from 1 to 630 A and over. Cable feed 
through.
•  Precise motor heating and cooling memory, reproduces 
its thermal image.
• Visual indication of tripping cause.
• Manual, remote and automatic reset.
Suitable where the undercurrent (running without load) is 
critical, such us submersible pumps, surface pumps, etc. In 
these cases, when the equipment runs without load (dry well) 
the relay trips by undercurrent.
The great advantage of the P relay is that, without requiring 
any external detectors such as level electrodes, it monitors the 
load of the motor and stops it before an expensive breakdown 
occurs.
By means of this plug-in optional accessory, the relay status 
can be seen and reset from the exterior of the electrical panel 
board.
Easy to install. Size of a Ø22 mm push button.
Suitable for motor control centres (MCC) and panel boards.
EXTERNAL DISPLAY MODULE
THREE PHASE PUMP PROTECTION
Underload protection by undercurrent
ELECTRONIC PROTECTION & CONTROL OF MOTORS, GENERATORS AND PUMPS