Tele 1341400 E3YF400VFAL02 Gamma 3-Phase Voltage Monitoring Relay, VDE 3-phase voltage monitoring according to VDE 0126- 1341400 Data Sheet

Product codes
1341400
Page of 2
Subject to alterations and errors
Release 07/07
Monitoring relays - ENYA series
Voltage monitoring in 3-phase mains in accordance with VDE 0126-1-1
Quick net error recognition
Supply voltage = measured voltage
2 change over contacts
Width 35mm
Installation design
Technical data
1. Functions
Voltage monitoring in 3-phase mains in accordance with VDE 0126-1-1 
with fi xed tripping delay, fi xed threshold, adjustable 10-minutes-average 
and selectable fault latch by means of rotary switch.
WIN  
Monitoring 
the 
fi xed adjusted range
WIN+Latch Monitoring 
the 
fi xed adjusted range with fault latch
2. Time ranges
  
 
Adjustment 
range
Tripping delay (ON-Delay): 
      fixed, 30s
Switch-off delay: 
 U 
≤ 80% of U
N
 
      < 200ms
 U 
≥ 115% of U
N
 
      < 200ms
 
phase failure 
      < 20ms
3. Indicators
     Green LED ON/OFF:   
indication of supply voltage
     Yellow LED ON/OFF:   
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required), 
IP rating IP20
Tightening torque: 
max. 1Nm
Terminals capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: 
(= measured voltage)
Terminals: (N)-L1-L2-L3
Rated voltage Un: 
see table ordering information or 
 
printing on the unit
Tolerance: 
-30% to +30% of Un
Rated consumption: 
11VA (1,2W)
Rated frequency: 
AC 48 to 63Hz
Duty cycle: 
100%
Reset time: 
500ms
Hold-up time: 
-
Drop-out voltage: 
determined by measuring function
 
(see measuring circuit)
Overvoltage category: 
III (in accordance with IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
2 potential free change over contacts
Rated voltage: 
250V AC
Switching capacity: 
1250VA AC1 B300/P300
 
(in accordance with IEC 60947-5-1)
 
therm. constant current 5A
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 6/min at 1000VA resistive load
 
(in accordance with IEC 60947-5-1)
Overvoltage category: 
III. (in accordance with IEC 60664-1)
Rated surge voltage: 
4kV
7. Measuring circuit
Measured variable: 
3(N)~, sinus, 48 to 63Hz
Measured input: 
(= supply voltage)
Terminals: (N)-L1-L2-L3
Overload capacity: 
determined by tolerance 
 specifi ed for supply voltage
Input resistance: 
-
Switching threshold Us: 
see table ordering information or
 
printing on the unit
10-minutes-average: 
see table ordering information or
 
printing on the unit
Overvoltage category: 
III (in accordance with IEC 60664-1)
Rated surge voltage: 
4kV
8. Accuracy
Base accuracy: 
<2% 
Adjustment accuracy: 
-
Repetition accuracy: 
≤1%
Voltage influence: 
-
Temperature influence: 
≤0,05% / °C
9. Ambient conditions
Ambient temperature: 
-25 to +55°C
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(in accordance with IEC 60721-3-3  
 class 
3K3)
Pollution degree: 
2, if built in 3
 
(in accordance with IEC 60664-1)
10. Weight
Single packing: 
 
94g
E3YF400VFAL02