Fanox 11243 C45 Motor Protection Relay, Basic Protection 11243 Data Sheet

Product codes
11243
Page of 1
10
•  For 3-phase motors from 1 to 630 A and over. Cable feed 
through relay.
•  Precise motor heating and cooling memory, reproduces 
its thermal image.
•  Immediate detection of phase loss (3 s), even at reduced 
load.
• Visual indication of tripping cause.
For motors of low and medium power in several applications 
such as compressors, ventilators, surface mounted pumps, 
conveyor belts, machine tools, and in general to protect 
motors which need dependable and accurate protection 
relays for every type of start.
Its 3 trip classes cover many types of starting or working 
cycles.
By means of this plug-in optional accessory, the relay status 
can be seen and reset from the exterior of the electrical panel 
board.
Easy to install. Size of a Ø22 mm push button.
Suitable for motor control centres (MCC) and panel boards.
Models
Code
Relay type
ODC
12530
C
MODELS
C 9
C 21
C 45
Adjustment range
 Motor 400 V
 50/60 Hz
I
B
 (A)
3 - 9,3
9 - 21,6
20 - 45,2
CV
2 - 5,5
7,5 - 12
15 - 30
kW
1,5 - 4
5,5 - 9
11 - 22
Code
  
according to the 
relay voltage supply 
(+15% -10%) 
ac: 50/60 Hz
230 Vac 
single phase
11203
11223
11243
115 Vac 
single phase
11202
11222
11242
24 Vac, dc single phase
11200
11220
11240
For 
,
N
 
of the motor below the minimum setting
 
,
B
Pass the cables several times (n) through the holes in the relay
 
,
B
 = n x 
,
N
For 
,
N
 
of the motor below the minimum setting
 
,
B
Use 3 CT .../5 and the relay C9 and pass the secondary twice through the holes
External display module (optional)
ODC
CHARACTERISTICS
Thermal memory / Overload trip
Yes / From 1,1 x 
,
B
Maximum motor nominal voltage
1000 Vac
Trip classes (IEC 947-4-1)
10 - 20 - 30
Phase imbalance protection
Over 40%. Tripping time < 3s
Reset mode
Manual and remote
Signalling LED’s
3 LED’s: ON +   + 
Output contacts
1 relay with 1 NO + 1 NC
Switching power 
,
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
Terminals: Max. section / screw torque
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
Power consumption
C9: 6,5VA (230Vac) - 3VA (115Vac) / C21-C45: 2,5VA
Protection degree / weight / mounting
IP20 / 0,3 kg / DIN rail
Storage temperature
-30°C +70°C
Operation temperature / max. altitude
-15°C +60°C / 1000m ; -15°C +50°C / 3000m
Standards
IEC 255, IEC 947, IEC 801, EN 50081-2
   
BASIC MOTOR PROTECTION
EXTERNAL DISPLAY MODULE
DIMENSIONS C RELAY (mm)
DIMENSIONS ODC MODULE (mm)
WIRING DIAGRAMS (mm)
C
  Overload
  Phase imbalance 
or phase loss
ODC
45
79
8
12
Ø 22,5
Ø 30,0
39
95
90
5
44
11,3
20,0
1 = 2 m
38
35,4
12
8
L3
L2
L1
13
M
14
A2
A2
N
K1
A1
A1
L1
13-K1
14-K1
97
98
95
96
Tripped
or Us=0
Normal
96
96
95
95
98
98
97
97
Settings and curves,see pages 24 to 29.
Motor protection relays
PROTECTION
FUNCTIONS
www.fanox.com
fanox@fanox.com
Tlf. +34 94 471 14 09
Fax +34 94 471 05 92
10/2010/D00