Phoenix Contact Overvoltage in AP-housing PLI-24 IP54 2838759 Data Sheet

Product codes
2838759
Page of 7
Nov 14, 2013    2 / 7
Technical data
Protective circuit, power supply
Nominal voltage U
N
230 V AC
Arrester rated voltage U
C
260 V AC
Nominal frequency f
N
50 Hz (60 Hz)
Nominal current I
N
16 A (≤ 45°C)
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
 (8/20) µs
1.5 kA
Nominal discharge current I
n
 (8/20) µs (L-N)
1.5 kA
Nominal discharge current I
n
 (8/20) µs (L-PE)
1.5 kA
Combined surge U
OC
4 kV
Energy absorption
80 J (L-N)
Voltage protection level U
P
 (L-N)
≤ 1.3 kV
Voltage protection level U
P
 (L-PE)
≤ 1.5 kV
Voltage protection level U
P
 (N-PE)
≤ 1.5 kV
Total surge current (8/20) µs
5 kA
Response time (L-N)
≤ 25 ns
Response time (L-PE)
≤ 100 ns
Response time (N-PE)
≤ 100 ns
Message: Surge protection fault
Optical, remote indicator contact
Max. required back-up fuse
16 A (gL)
Connection (protective circuit, power supply)
Connection method
Screw terminal blocks
Connection type IN
Screw terminal blocks
Connection type OUT
Screw terminal blocks
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Remote indicator contact (protective circuit, power
supply)
Connection name
Remote fault indicator contact
Switching function
N/C contact
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
16
Maximum operating voltage U
max.
 AC
250 V AC