Suevia DIN rail mount timer analogue UNO QRD 230 Vac 16 A/250 V UNO QRD Data Sheet

Product codes
UNO QRD
Page of 1
MANUAL MODE
PROGRAMMING
DIAL
INDEX
 
MODULAR TIME SWITCH 
uno
 
OPERATING INSTRUCTIONS 
 
 
 
 
 
 
 
 
 
DESCRIPTION 
The UNO time switch controls any electrical installation by means of daily or weekly  
programs. 
INSTALLATION 
ATTENTION: Electrical devices must be installed and assembled by an authorized 
installer.  Electronic  automatic  control,  independent  mounting  in  distribution  cabinet 
fitted  with  a  35mm  symmetric  profile  in  accordance  DIN  EN  60715  standard  (DIN 
Rail). 
VERY  IMPORTANT:  The  switch  is  protected  internally  against  interference  by  a 
safety  device.  However,  particularly  strong  electromagnetic  fields  may  alter  its 
operation. 
Such  interference  can  be  avoided  by  adhering  to  the  following  recommendations 
during installation: 
-  The  device  should  not  be  installed  near  inductive  loads  (motors,  transformers, 
contactors, etc.). 
-  A  separate  power  line  is  recommended  (equipped  with  a  network  filter  if 
necessary). 
- Inductive loads should be equipped with interference suppressors (varistor,  
RC filter). 
If the timer switch is to be used in combination with other devices in an installation, it is 
necessary to verify that no parasitic disturbances will be caused by the group. 
CONNECTION
: Connection scheme 
 
 
 
 
PROGRAMMING: 
Take  over  all  the  pins  to  the  right.  Take  over  to  the  left  the  pins  corresponding  to 
the desired times of connection, in which the contact 1-2 will be closed. 
HOUR UPDATING: 
Turn the dial until the index is on the current time.   
MANUAL MODE: 
2 positions: 
 
 
   Automatic functioning 
  
 Ι    Permanent connection  
 
TECHNICAL SPECIFICATIONS: 
Supply voltage: 
Follow the indications 
Switching capability: 
 
   16 (4) A / 250 V~ 
Type of action 
 
   1B, 1T, 1U, 1R (D and S) in accordance  
 
 
 
    EN 60730-2-7 
 
 
 
   1B, 1T, 1U, 1S (QRD and QRS) in accordance 
 
 
 
    EN 60730-2-7 
Power consumption: 
0.5 W 
Operating accuracy: 
 
    ± 1 sec./day at 22ºC 
Power reserve  
Type D: without reserve 
 
 
Type QRD and QRS: 100 hours after 
 
 
uninterrupted supply of 48 hours 
Type of dial: 
 
    Daily: 96 pins 
 
 
 
 
 
    Weekly: 84 pins 
Minimum time of functioning: 
    Daily: 15 minutes 
 
 
 
    Weekly: 2 hours 
Switching accuracy: 
Daily: ± 5 minutes 
 
 
 
   Weekly: ± 30 minutes 
Functioning temperature: 
    -10 ºC  to  +45 ºC 
Protection category: 
 
    IP 20 in accordance with  
    EN 60529 
Protection class 
 
    II in accordance with EN 60335  
 
   under correct assembling conditions 
Control pollution situation: 
   Normal 
DIMENSIONS: 
 
 
 
 
 
 
 
 
 
 
 
ATTENTION 
This  unit  incorporates  a  battery  containing  contents  that  can  be  harmful  to  the 
environment.  Please  do  not  throw  it away without removing the battery and putting 
it in the proper container for recycled batteries or to send the complete unit back to 
the factory.  
 
Suevia Zeitschalttechnik GmbH 
 
Robert-Bosch-Str. 3 
 
D-71088 Holzgerlingen 
Telefon 0 70 31 / 86 65 –0 
Telefax 0 70 31 / 86 65 –10 
L
N
1
2
M
UNO
OFF
OFF
ON
6
5
17.5
9
0
4
5
60
66