MEAN WELL MDR-40-24 Data Sheet

Page of 2
SPECIFICATION
MDR-40-5
MDR-40-12
MDR-40-24
MDR-40-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
Note.5
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING HUMIDITY
WORKING TEMP.
DC OK SIGNAL
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
5V
12V
24V
48V
6A
3.33A
1.7A
0.83A
0 ~ 6A
0 ~ 3.33A
0 ~ 1.7A
0 ~ 0.83A
30W
40W
40.8W
39.8W
80mVp-p
120mVp-p
150mVp-p
24 ~ 30V
200mVp-p
48 ~ 56V
±2.0%
±1.0%
±1.0%
±1.0%
12 ~ 15V
5 ~ 6V
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
500ms, 30ms/230VAC          500ms, 30ms/115VAC at full load
50ms/230VAC          20ms/115VAC at full load
85 ~ 264VAC          120 ~ 370VDC
47 ~ 63Hz
78%
86%
88%
88%
1.1A/115VAC          0.7A/230VAC
COLD START 30A/115VAC          60A/230VAC
105 ~ 150% rated output power
Protection type :
Constant current limiting, recovers automatically after fault condition is removed
6.25 ~ 7.25V
Protection type : Shut down o/p voltage, re-power on to recover
15.6 ~ 18V
31.2 ~ 36V
57.6 ~ 64.8V
-20 ~ +70
(Refer to "Derating Curve")
Relay contact rating(max.): 30V/1A resistive
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
±
0.03%/
(0 ~ 50
)
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
301.7K hrs min.      MIL-HDBK-217F (25
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25  of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
    EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
    (as available on http://www.meanwell.com)
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-40-SPEC   2014-10-22
UL508, UL60950-1, TUV EN60950-1,
approved
Class I,  Div. 2 Group A, B, C, D Hazardous Locations T4
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
40W Single Output Industrial DIN Rail Power Supply
MDR-40
series
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
ENVIRONMENT
PROTECTION
SAFETY &
FUNCTION
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE

Universal AC input/Full range

Protections: Short circuit / Overload / Over voltage

Cooling by free air convection

Can be installed on DIN rail TS-35/7.5 or 15

Class I, Div 2 Hazardous Locations T4

LED indicator for power on

DC OK relay contact

No load power consumption<0.75W

100% full load burn-in test

3 years warranty
 Features :
40*90*100mm (W*H*D)
0.3Kg; 42pcs/13.6Kg/0.82CUFT
..
LEAKAGE CURRENT
<1mA / 240VAC
I/P-O/P:3KVAC     I/P-FG:2KVAC     O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25
/ 70% RH
EMC IMMUNITY
EMC EMISSION