Finder 70.11.8.230.2022 Options: 1-phase mains monitoring (220 – 240 V/AC), undervoltage, overvoltage, over/under voltag 70.11.8.230.2022 Data Sheet

Product codes
70.11.8.230.2022
Page of 14
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
4b
UV
UVm*
Umax
Umax -H
LED 1
LED 2
LED 1
LED 2
4a
OV
OVm*
Umax
Umax -H
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
1
3a
3b
3d
3c
3e
3f
70.11
www.findernet.com
2
(1x6/2x4) mm
2
(1x10/2x12) AWG
(1x4/2x2.5) mm
2
(1x12/2x14) AWG
0.8 Nm
3
IP20
70.11.8.230.2022
U
N
: (220...240) V AC (50/60 Hz)
U
min
: 130 V AC
U
max
: 280 V AC
P: 2.6 VA / 0.8 W
1 CO (SPDT)
10 A 250 V AC
AC1                             2500 VA
AC15 (230 V AC)         750 VA
(230 V AC)         0.5 kW
DC1 (30 / 110 / 220)V   (10 / 0.3 / 0.12) A
(−20...+50) °C
IB7011001 - 08/12
4
4c
W
Wm*
1
~
M
70.11 - 1 PHASE AC LINE MONITORING RELAY
OUTLINE DRAWING
WIRING DIAGRAM
11-14: output Make contact
11-12: output Break contact
FRONT VIEW (detail)
3a
Function selector
UV
Undervoltage without memory
UVm Undervoltage with memory
OV
Overvoltage without memory
OVm Overvoltage with memory
W
Window Mode without memory
Wm Window Mode with memory
3b
LED 1 (green)
3c
Switch-off delay time (T on function diagrams) adjustable (0.5...60)s
3d
LED 2 (red)
3e
Maximum voltage selector (220...270)V
3f
Minimum voltage selector (170...230)V
FUNCTIONS
4a
Undervoltage (UV and UVm functions)
4b
Overvoltage (OV and OVm functions)
4c
Window mode (overvoltage + undervoltage, 
W and Wm functions)
NOTE
Hysteresis (H on function diagrams): 5V.
Power-on activation time: 1s.
Switch-on lock-out time: 0.5s.
Positive safety logic - Make output contact opens if the relay 
detects an error.
*
RESET MEMORY
To reset, It is necessary to switch the supply OFF and then ON
again (U OFF U ON) or to rotate the function selector first to an 
adjacent position and then to the original position.
1
2
3
4
   
ENGLISH