7.5 PROFINET 
 
Easy Book 
134
 
Manual, 03/2014, A5E02486774-AF 
7.5.1.1 
Ad hoc mode 
Typically, TCP and ISO-on-TCP receive data packets of a specified length, ranging from 1 to 
8192 bytes. However, the TRCV_C and TRCV communication instructions also provide an 
"ad hoc" communications mode that can receive data packets of a variable length from 1 to 
1472 bytes.  
 
 
Note 
If you store the data in an "optimized" DB (symbolic only), you can receive data only in 
arrays of Byte, Char, USInt, and SInt data types. 
 
To configure the TRCV_C or TRCV instruction for ad hoc mode, set the ADHOC instruction 
input parameter. 
If you do not call the TRCV_C or TRCV instruction in ad hoc mode frequently, you could 
receive more than one packet in one call. For example: If you were to receive five 100-byte 
packets with one call, TCP would deliver these five packets as one 500-byte packet, while 
ISO-on-TCP would restructure the packets into five 100-byte packets.  
7.5.1.2 
Connection IDs for the Open user communication instructions 
When you insert the TSEND_C, TRCV_C or TCON PROFINET instructions into your user 
program, STEP 7 creates an instance DB to configure the communications channel (or 
connection) between the devices. Use the "Properties" of the instruction to configure the 
parameters for the connection. Among the parameters is the connection ID for that 
connection.  
●  The connection ID must be unique for the CPU. Each connection that you create must 
have a different DB and connection ID. 
●  Both the local CPU and the partner CPU can use the same connection ID number for the 
same connection, but the connection ID numbers are not required to match. The 
connection ID number is relevant only for the PROFINET instructions within the user 
program of the individual CPU. 
●  You can use any number for the connection ID of the CPU. However, configuring the 
connection IDs sequentially from "1" provides an easy method for tracking the number of 
connections in use for a specific CPU. 
 
 
 
Note 
Each TSEND_C, TRCV_C or TCON instruction in your user program creates a new 
connection. It is important to use the correct connection ID for each connection.