8.4 PID_3Step instruction 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
179
 
8.4 
PID_3Step instruction 
The PID_3Step instruction configures a PID controller with self-tuning capabilities that has 
been optimized for motor-controlled valves and actuators.  
Table 8- 6 
PID_3Step instruction 
LAD / FBD 
SCL 
Description 
 
"PID_3Step_1"( 
    SetpoInt:=_real_in_, 
    Input:=_real_in_, 
    ManualValue:=_real_in_, 
    Feedback:=_real_in_, 
    InputPer:=_word_in_, 
    FeedbackPer:=_word_in_, 
 Disturbance:=_real_in_, 
 ManualEnable:=_bool_in_, 
    ManualUP:=_bool_in_, 
    ManualDN:=_bool_in_, 
    ActuatorH:=_bool_in_, 
    ActuatorL:=_bool_in_, 
    ErrorAck:=_bool_in_, 
 Reset:=_bool_in_, 
    ModeActivate:=_bool_in_, 
 Mode:=_int_in_, 
 ScaledInput=>_real_out_, 
    ScaledFeedback=>_real_out_, 
    ErrorBits=>_dword_out_, 
    OutputPer=>_word_out_, 
    State=>_int_out_, 
    OutputUP=>_bool_out_, 
    OutputDN=>_bool_out_, 
    SetpoIntLimitH=>_bool_out_, 
    SetpoIntLimitL=>_bool_out_, 
    InputWarningH=>_bool_out_, 
    InputWarningL=>_bool_out_, 
    Error=>_bool_out_, 
 ErrorBits=>_dword_out_); 
PID_3Step configures a PID controller with 
self-tuning capabilities that has been 
optimized for motor-controlled valves and 
actuators. It provides two Boolean outputs.  
PID_3Step is a PID T1controller with anti-
windup and weighting of the P- and D-
components.  
 
1
  STEP 7 automatically creates the technology object and instance DB when you insert the instruction. The instance DB 
contains the parameters of the technology object. 
2
  In the SCL example, "PID_3Step_1" is the name of the instance DB.