8.6 Configuring the PID controller 
 
Easy Book 
188
 
Manual, 03/2014, A5E02486774-AF 
8.6 
Configuring the PID controller 
 
The parameters of the technology object determine the operation of the PID 
controller. Use the icon to open the configuration editor. 
 
 
Table 8- 9 
Sample configuration settings for the PID_Compact instruction 
Settings 
Description 
Basic 
Controller type 
Selects the engineering units. 
Invert the control logic  Allows selection of a reverse-acting PID loop. 
 
If not selected, the PID loop is in direct-acting mode and the output of PID loop 
increases if input value < setpoint. 
 
If selected, the output of the PID loop increases if the input value > setpoint. 
Enable last mode after 
CPU restart 
Restarts the PID loop after it is reset or if an input limit has been exceeded and 
returned to the valid range. 
Input 
Selects either the Input parameter or the Input_PER parameter (for analog) for the 
process value. Input_PER can come directly from an analog input module. 
Output 
Selects either the Output parameter or the Output_PER parameter (for analog) for 
the output value. Output_PER can go directly to an analog output module. 
Process 
value 
Scales both the range and the limits for the process value. If the process value goes below the low limit or 
above the high limit, the PID loop goes to inactive mode and sets the output value to 0. 
To use Input_PER, you must scale the analog process value (input value).