A.4 Specifications for the digital inputs and outputs 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
303
 
 
 
Note 
When switching frequencies above 20 KHz, it is important that the digital inputs receive a 
square wave. Consider the following options to improve the signal quality to the inputs: 
 
Minimize the cable length 
 
Change a driver from a sink only driver to a sinking and sourcing driver 
 
Change to a higher quality cable 
 
Reduce the circuit/components from 24 V to 5 V 
 
Add an external load at the input 
 
 
Table A- 26  HSC clock input rates (max.) 
Technical data 
Single phase 
Quadrature phase 
CPU 1211C 
100 KHz 
80 KHz 
CPU 1212C 
100 KHz (Ia.0 to Ia.5) and  
30 KHz (Ia.6 to Ia.7) 
80 KHz (Ia.0 to Ia.5) and  
20 KHz (Ia.6 to Ia.7) 
CPU 1214C, CPU 1215C 
100 KHz (Ia.0 to Ia.5) and  
30 KHz (Ia.6 to Ib.5) 
80 KHz (Ia.0 to Ia.5) and  
20 KHz (Ia.6 to Ib.5) 
CPU 1217C 
1 MHz (DIb.2 to DIb.5) 
1 MHz (DIb.2 to DIb.5) 
High-speed (200 KHz) SB 
200 kHz 
160 kHz 
Standard-speed SB 
30 kHz 
20 kHz 
 
1
  Logic 1 level = 15 to 26 VDC 
A.4.2 
120/230 VAC digital AC inputs 
Table A- 27  120/230 VAC digital inputs 
Technical data 
SM 
Type 
IEC Type 1 
Rated voltage 
120 VAC at 6 mA, 230 VAC at 9 mA 
Continuous permissible voltage 
264 VAC 
Surge voltage 
N/A 
Logic 1 signal (min.) 
79 VAC at 2.5 mA 
Logic 0 signal (max.) 
20 VAC at 1 mA 
Leakage current (max.) 
1 mA 
Isolation (field side to logic) 
1500 VAC for 1 minute  
Isolation groups
1
 
Input delay times 
 
Typical: 0.2 to 12.8 ms, user selectable 
 
Maximum: -- 
Connection of 2 wire proximity sensor (Bero) (max.) 
1 mA