Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 User Manual

Product codes
6AV6651-7KA01-3AA4
Page of 364
Technical specifications 
 
A.8 RTD and Thermocouple modules 
 
Easy Book 
318
 
Manual, 03/2014, A5E02486774-AF 
 
Note 
After power is applied, the module performs internal calibration for the analog-to-digital 
converter. During this time the module reports a value of 32767 on each channel until valid 
data is available on that channel. Your user program may need to allow for this initialization 
time. Because the configuration of the module can vary the length of the initialization time, 
you should verify the behavior of the module in your configuration. If required, you can 
include logic in your user program to accommodate the initialization time of the module. 
 
A.8.1 
SB 1231 RTD and SB 1231 TC specifications 
 
 
Note 
To use these TC and RTD SBs, your CPU firmware must be V2.0 or higher. 
 
 
Table A- 47  General specifications 
Technical data 
SB 1231 AI 1 x16 bit TC 
SB 1231 AI 1 x 16 bit RTD 
Order number 
6ES7 231-5QA30-0XB0 
6ES7 231-5PA30-0XB0 
Dimensions W x H x D (mm) 
38 x 62 x 21 mm  
38 x 62 x 21 mm 
Weight 
35 grams 
35 grams 
Power dissipation 
0.5 W 
0.7 W 
Current consumption (SM Bus) 
5 mA 
5 mA 
Current consumption (24 VDC) 
20 mA 
25 mA 
Number of inputs (Page 323)  
Type 

Floating TC and mV 

Module-referenced RTD and Ω 
Diagnostics 
 
Overflow / underflow
1, 2
 
 
Wire break
3
 
 
Overflow / underflow
1, 2
 
 
Wire break
3
 
 
1
  The overflow and underflow diagnostic alarm information will be reported in the analog data values even if the alarms 
are disabled in the module configuration. 
  RTD: For resistance ranges, underflow detection is never enabled.
 
 
3
  When wire break alarm is disabled and an open wire condition exists in the sensor wiring, the module may report 
random values.