Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 User Manual

Product codes
6AV6651-7KA01-3AA4
Page of 364
Technical specifications 
 
A.9 Communication interfaces 
 
Easy Book 
338
 
Manual, 03/2014, A5E02486774-AF 
Table A- 71  RS485 or RS422 connector (female) 
Pin 
Description 
Connector  
(female) 
Pin 
Description 
Logic or communication ground 
 
6 PWR 
+5 V with 100 ohm series resistor: Output 
2 TxD+ 
1
  Connected for RS422 
Not used for RS485: Output 
Not connected 
3 TxD+ 
Signal B (RxD/TxD+): Input/Output 
8 TXD- 
Signal A (RxD/TxD-): Input/Output 
4 RTS 
2
 
Request to send (TTL level) Output 
9 TXD- 
1
  Connected for RS422 
Not used for RS485: Output 
5 GND 
Logic or communication ground 
SHELL 
Chassis ground 
 
  Pins 2 and 9 are only used as transmit signals for RS422. 
2
  The RTS is a TTL level signal and can be used to control another half duplex device based on this signal. It is active 
when you transmit and is inactive all other times.  
A.9.4.3 
CM 1241 RS232 specifications 
Table A- 72  General specifications 
Technical data 
CM 1241 RS232 
Order number  
6ES7 241-1AH32-0XB0  
Dimensions (mm) 
30 x 100 x 75 
Weight 
150 grams 
 
Table A- 73  Transmitter and receiver 
Technical data 
CM 1241 RS232 
Type 
RS232 (full-duplex) 
Transmitter output voltage 
+/- 5 V min. at R
L
 = 3K Ω 
Transmit output voltage 
+/- 15 VDC max. 
Receiver input impedance 
3 K Ω min. 
Receiver threshold/sensitivity 
0.8 V min. low, 2.4 max. high 
0.5 V typical hysteresis 
Receiver input voltage 
+/- 30 VDC max.  
Isolation 
RS 232 signal to chassis ground 
RS 232 signal to CPU logic common 
500 VAC, 1 minute 
Cable length, shielded 
10 m max. 
Baud rate 
300 baud, 600 baud, 1.2 kbits, 2.4 kbits, 4.8 kbits, 9.6 kbits (default), 
19.2 kbits, 38.4 kbits, 57.6 kbits, 76.8 kbits, 115.2 kbits,  
Parity 
No parity (default), even, odd, Mark (parity bit always set to 1), 
Space (parity bit always set to 0) 
Number of stop bits 
1 (default), 2