Rules 
●  Overlaying of tags is only possible in FB and FC blocks with standard access. 
●  You can overlay parameters for all block types and all declaration sections. 
●  An overlaid parameter can be used like any other block parameter. 
●  You cannot overlay parameters of type VARIANT. 
●  The size of the overlaying parameter must be less than or equal to the size of the overlaid 
parameter. 
●  The overlaying variable must be declared immediately after the variable that it overlays 
and identified with the keyword "AT". 
4.5 
Pulse outputs 
The CPU or signal board (SB) can be configured to provide four pulse generators for 
controlling high-speed pulse output functions, either as pulse-width modulation (PWM) or as 
pulse-train output (PTO). The basic motion instructions use PTO outputs. You can assign 
each pulse generator to either PWM or PTO, but not both at the same time.  
 
 
Pulse outputs cannot be used by other instructions in the 
user program. When you configure the outputs of the 
CPU or SB as pulse generators, the corresponding 
output addresses are removed from the Q memory and 
cannot be used for other purposes in your user program. 
If your user program writes a value to an output used as 
a pulse generator, the CPU does not write that value to 
the physical output.