Tripp Lite SmartOnline 120V 3kVA 2.4kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack/Tower, USB, DB9 Serial SU3000RTXL3U Data Sheet

Product codes
SU3000RTXL3U
Page of 6
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types
Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 110/120V (+/-2%) values
Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W)
Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible)
external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Compact rackmount form factor installs using only 3 rack spaces (3U) with a maximum installed depth of 26 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITHD enables 2 post rackmount installation (not wallmount compatible)
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number
of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery
capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment
and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA L5-30P input plug; NEMA 5-15/20R & L5-30R output receptacles
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each bank has four
outlets)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations; no time consuming connection of internal batteries by user required
Single line TEL/DSL or network ethernet line surge suppression
$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)
Specifications
OUTPUT
Output Capacity Details
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Output Volt Amp Capacity (VA)
3000
Output kVA Capacity (kVA)
3
Output Watt Capacity (Watts)
2400
Output kW Capacity (kW)
2.4
Power Factor
0.8
Crest Factor
3:1