Tripp Lite SmartOnline 200-240V 12kVA 10.8kW On-Line Double-Conversion UPS, N+1, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial, Hardwire SU12KRT4UHW Data Sheet

Product codes
SU12KRT4UHW
Page of 6
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load)
63.8A (200V), 61.2A (208V), 58A (220V), 55.4A (230V), 53.2A (240V)
Nominal Input Voltage(s) Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type
Hardwire
UPS Input Connection Description
Supports North American 208/240V input (L1,L2,G) and International 230/220/240V (L,N,PE) input wiring
Recommended Electrical Service
70A
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
2 minutes (10,800 watts)
Half Load Runtime (min.)
8.5 minutes (5400 watts)
Expandable Battery Runtime
Runtime is expandable with external battery packs
External Battery Pack Compatibility
Expandable Runtime Description
For best results, add external batteries in multiples of two so that both included 6kVA power modules have an equal
number and type of connected battery packs
DC System Voltage (VDC)
192
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
Each of the two included 6kVA power modules contain one 
Battery Access
Front panel battery access door
Battery Replacement Description
Hot-swappable, user replaceable internal battery cartridges and external battery packs
VOLTAGE REGULATION
Voltage Regulation Description
+/-2% output voltage regulation in standard online, double-conversion mode
Overvoltage Correction
Corrects overvoltages as high as 300V (<90% load) and 280V (full load)
Undervoltage Correction
Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Switches
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass
switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without
disrupting power to connected loads
Alarm Cancel Operation
Alarm cancel switch
Audible Alarm
Unique audible alarms for all major UPS, environmental and power conditions (see manual)
3 / 6