Tripp Lite SmartOnline 110-120V 3kVA 2.4kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack/Tower, USB, DB9 Serial, Hardwire SU3000RTXR3UHW Data Sheet

Product codes
SU3000RTXR3UHW
Page of 6
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types
Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 110/120V (+/-2%) values
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
Internal battery set offers 30 minutes runtime at half load (1200W) and 12 minutes at full load (2400W)
Optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible) external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Compact rackmount form factor installs using only 3 rack spaces (3U) with a maximum installed depth of 26 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITHD enables 2 post rackmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial/contact-closure and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number
of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery
capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment
and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
Hardwire 120V AC input/output (L-N-G)
Front panel LEDs offer current monitoring and battery charge level information
Single line TEL/DSL or network ethernet line surge suppression
$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)
Specifications
OUTPUT
Output Capacity Details
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Output Volt Amp Capacity (VA)
3000
Output kVA Capacity (kVA)
3
Output Watt Capacity (Watts)
2400
Output kW Capacity (kW)
2.4
Power Factor
0.8
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
110V; 120V
Nominal Voltage Details
120V default
Frequency Compatibility
50 / 60 Hz
2 / 6