Tripp Lite SmartOnline 100-127V 1kVA 900W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, LCD display, USB, DB9 Serial SU1000RTXLCD2U Data Sheet

Product codes
SU1000RTXLCD2U
Page of 6
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles
(6) 5-15R
UPS Output Receptacles (Surge
Suppression Only)
ON LINE MODE: Maximum output capacity is reduced to 608 watts at 100V nominal; FREQUENCY / REGULATION
CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode
(127/120/115/110V 630 watts / 100V 567 watts). OVERLOAD CAPACITY: Supports inverter operation up to 105%
load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before
switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when
bypass input voltage or frequency are OUTSIDE bypass limits)
Load Management Receptacles
Two switchable single-outlet 5-15R load banks
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load)
8.6A
Nominal Input Voltage(s) Supported
100V AC; 110V AC; 115V AC; 120V AC; 127V AC
Nominal Input Voltage Description
120V factory default
UPS Input Connection Type
5-15P
Input Circuit Breakers
15A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3
Recommended Electrical Service
15A 120V
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
4.8 min. (900w)
Half Load Runtime (min.)
14 min. (450w)
Expandable Battery Runtime
Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
(limit 1); 
(limit 1); 
compatible)
Expandable Runtime Description
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software, see
manual for details
DC System Voltage (VDC)
24
Battery Recharge Rate (Included
Batteries)
Less than 3 hours recharge to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
3 / 6