Tripp Lite SmartOnline 100-127V 1kVA 900W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, LCD display, USB, DB9 Serial SU1000XLCD Data Sheet

Product codes
SU1000XLCD
Page of 6
Specifications
OUTPUT
Output Capacity Details
ON LINE MODE: Maximum output capacity rating is reduced to 810W at 100V nominal; FREQUENCY
REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion
mode (127/120/115/110V 630 watts / 100V 567 watts) OVERLOAD CAPACITY: Supports inverter operation up to
105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds
before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN
(when bypass input voltage or frequency are OUTSIDE bypass limits)
Output Volt Amp Capacity (VA)
1000
Output kVA Capacity (kVA)
1
Output Watt Capacity (Watts)
900
Power Factor
0.9
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
100V; 110V; 120V; 127V
Nominal Voltage Details
120V default
Frequency Compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
when input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
BATTERY MODE: Output is regulated to +/-0.05Hz of selected nominal.
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles
(6) 5-15R
UPS Output Receptacles (Surge
Suppression Only)
ON LINE MODE: Maximum output capacity rating is reduced to 810W at 100V nominal; FREQUENCY
REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion
mode (127/120/115/110V 630 watts / 100V 567 watts) OVERLOAD CAPACITY: Supports inverter operation up to
105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds
before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN
(when bypass input voltage or frequency are OUTSIDE bypass limits)
Load Management Receptacles
Two switchable single-outlet 5-15R load banks
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load)
10A
Nominal Input Voltage(s) Supported
100V AC; 110V AC; 120V AC; 127V AC
3 / 6