Burnham Series C Power Flame Low NOx Data Sheet

Page of 1
Low Nox Power Flame Burner Information
Burner Model
Motor
Firing Sequence
 [1]
Gas Train
Horsepower
Boiler Size
Gas and Gas/#2 Oil
Gas
Voltage
Gas
Gas/#2 Oil
Size
Min. Pres. Max. Pres.
C-20
LNIC1-*-12
1/3
115/60/1
L-H-O
RM7895C/UV
1
4.3" w.c. 
14.0" w.c.
C-30
LNIC2-*-20A
1/2
115/60/1
L-H-O
RM7895C/UV
1
1/4
6.0" w.c. 
14.0" w.c.
C-40
LNIC2-*-20B
1/2
115/60/1
L-H-O
RM7895C/UV
1
1/4
5.5" w.c. 
14.0" w.c.
C-50
LNIC2-*-20B
3/4
230/60/1
L-H-O
RM7895C/UV 1
1/2 / 
1
1/4
8.3" w.c. 
14.0" w.c.
C-60
LNIC3-*-20
3/4
208/460/3
L-H-O
RM7840L/UV
2 / 1
1/2
7.3" w.c. 
14.0" w.c.
C-70
LNIC3-*-20
3/4
208/460/3
L-H-O
RM7840L/UV
2 / 1
1/2
6.1" w.c. 
14.0" w.c.
C-80
LNIC3-*-25
1
1/2
208/460/3
L-H-O
RM7840L/UV
2 / 1
1/2
7.7" w.c. 
14.0" w.c.
C-90
LNIC4-*-25
1
1/2
208/460/3
L-H-O
RM7840L/UV
2
8.2" w.c. 
14.0" w.c.
C-100
LNIC4-*-30
3
208/460/3
L-H-O
RM7840L/UV
2
7.7" w.c. 
14.0" w.c.
C-125
LNIC5-G/GO-30
5
208/460/3
MOD
RM7840L/UV
2
10.7" w.c.
14.0" w.c.
C-150
LNIC6-G/GO-30
10
208/460/3
MOD
RM7840L/UV
2 1/2
10.9" w.c.
28.0" w.c.
C-175
LNIC6-G/GO-30
10
208/460/3
MOD
RM7840L/UV
3
11.4" w.c.
28.0" w.c.
C-200
LNICMR9B-G/GO-30*
10
208/460/3
MOD
RM7840L/UV
3
12.5" w.c.
28.0" w.c.
[1]  Explanation of Firing Sequences:
Gas and Gas Sequence on Combination Gas/Oil Boilers
L-H-O
Slow opening gas valve, adjustable position (LFS) air damper, linked to motorized gas valve.
Oil and Oil Sequence on Combination Gas/Oil Boilers
L-H-O
Adjustable air damper (spring close), linked to oil pressure cylinder, oil pressure regulator and 
 by-pass valve for LFS.
[2]  Model C-50  - Dual size gas trains:  Leak test cock and main gas valve are indicated by the first number; 
     combination gas valve/regulator and main shutoff cock are indicated by the second number.
[3]  Models C-60-C-80 - Dual size gas trains:  Leak test cock, main gas valve and auxiliary gas valve are indicated 
     by the first number; gas regulator and main shutoff cock are indicated by the second number.
* LNICMR9B Burner is required for C-200 due to base interference and davited front smokebox doors are required. 
LNC SERIES