Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page of 64
SED2 VFD Electronic Bypass Option Operating Instructions 
26 
 
Siemens Building Technologies, Inc. 
 
Parameter Description 
Action 
Setting/ 
Default 
P0640 
Motor Overload Factor 
10% to 400% 
Limited to the maximum SED2 
output current rating, or to 400% 
of the rated current (P0305), 
whichever is lower. 
NOTE: 
This parameter is available when 
P0003 = 3 and  
P0010 = 1. 
1. Press   to advance to 
parameter P0640
2. Press   to access the 
parameter values level. 
3. Press   to advance to 
desired value. 
4. Press   to confirm and save 
the setting. 
Setting =  
As applicable 
Default = 110 
P0700(0)** 
Selection of Command Source 
(Start Command) 
Selects the command source as 
follows: 
0 = Factory default setting 
1 = BOP (keypad) 
2 = Terminal digital input 
4 = USS on BOP link (AOP) 
5 = USS on COM link 
6 = CB (Communications board 
or module) on COM link (P1/N2) 
1. Press   to advance to 
parameter P0700
2.   Press 
 to access the 
parameter indexes. 
3. Press   to advance to index 
[0], IN000, AUTO. 
4. Press   to confirm index 
selection. 
5. Press   to advance to 2
6. Press   to confirm and save 
the setting. 
Setting = 2 
Default = 2 
NOTE: 
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 
to 2 resets all digital inputs to default settings. 
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.