Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page of 64
Startup Procedures 
Siemens Building Technologies, Inc. 
 
29 
 
Parameter Description 
Action 
Setting/ 
Default 
P1082 
Maximum Motor Frequency 
0 Hz to 650 Hz 
Maximum motor frequency at 
which the motor will run 
regardless of the frequency 
setpoint. This value applies to 
both clockwise and 
counterclockwise rotation. 
1. Press   to advance to 
parameter P1082
2. Press   to access the 
parameter values level. 
3. Press   to advance it desired 
value. 
4. Press   to confirm and save 
the setting. 
Site Setting 
Default = 50 or 
60 
(Default is 
determined by 
the setting of 
the motor 
frequency and 
unit of 
measurement 
DIP switches.) 
NOTE: 
This value is limited internally to 200 Hz or five times the rated motor frequency (P0305). When P1300 is 
greater than or equal to 20 (control mode = vector control), the value displays via r0209 (maximum 
frequency). 
P1120 
Ramp-up Time
 
0s to 650s 
1. Press   to advance to 
parameter P1120
2. Press   to access the 
parameter values level. 
3. Press   to advance it desired 
value. 
4. Press   to confirm and save 
the setting. 
Site Setting 
Default = 10 
Typical fan = 
120s 
Typical pump = 
30s 
NOTES:
 
1.  Setting the ramp-up time too short can cause the SED2 to trip (F0001 over current, F0002 over voltage, 
or F0003 under voltage). 
2.  If using an external frequency setpoint with set ramp rates (such as from a PLC), achieve optimum 
SED2 performance by setting ramp time (P1120 and P1121) slightly shorter than those of the PLC.