Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page of 64
SED2 VFD Electronic Bypass Option Operating Instructions 
32 
 
Siemens Building Technologies, Inc. 
Parameter Description 
Action 
Setting/ 
Default 
P1202 
Motor Current: Flying Start
 
Defines search current used for 
flying start. Value is in % based 
on the rated motor current 
(P0305).   
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1202.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired value.  
5. Press   to confirm and save 
the setting. 
Minimum = 10 
Default = 100 
Maximum = 
200 
NOTE: 
Reducing the search current may improve performance for flying start if the inertia of the system is not very 
high. 
P1203 
Search Rate: Flying Start
 
Sets factor by which the output 
frequency changes during flying 
start to synchronize with the 
turning motor. This value, 
entered in % relative to the 
default time factor, defines the 
initial gradient and influences the 
time taken to search for the 
motor frequency.  
The search time is the time taken 
to search through all frequencies 
between 
f_max + 2 × f_slip to 0 Hz.  
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1203.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired value.  
5. Press   to confirm and save 
the setting. 
Minimum = 10 
Default = 100 
Maximum = 
200 
NOTES: 
1.  P1203 = 100% is defined as giving a rate of 2% of f_slip, nom/ms. 
2.  P1203 = 200% would result in a rate of frequency change of 1% of f_slip, nom/ms. 
3.  A higher value produces a flatter gradient, and thus a longer search time. A lower value has the 
opposite effect.