Application Feature Setup 
Siemens Building Technologies, Inc. 
 
43 
NOTES: 
1.  All safety conditions must be met for bypass mode operation.  
2.  The input contactor remains energized.  
The Electronic Bypass Option will return to VFD mode operation as soon as the 
SED2 Relay in control opens. When the Electronic Bypass Option returns to VFD 
mode operation, the following occurs: 
•  The SED2 Relay opens, the Programmable Output on the Controller 
board opens, and the bypass contactor opens.  
•  The output contactor closes.  
NOTE: 
All safety conditions must be met for VFD mode operation. 
Settings 
The Auto Bypass feature requires that Controller board 
DIP Switch 2 is set ON. 
NOTE: 
During operation, the Auto Bypass Enabled 
indicator is on steady.  
ON
12
5
34
12
5
34
ON
OFF
SW1
VFD0117R1
 
Example SED2 Settings 
Set parameters P0732 and P0748 for Auto Bypass on Drive Fault. Programming of 
the SED2 Relay is required for proper Auto Bypass activation. Set P0732 and P0748 
as follows: 
 
Parameter Setting 
P0732 in000 
52.3 
P0732 in001 
52.3 
P0748