SERVICE HINTS
POWER ON 
STAND BY
THERMOSTAT
CALLS FOR HEAT
CIRCULATOR
ENERGIZES THRU
2K1 CONTACTS
IBC SELFCHECK OF 
INTERNAL CIRCUITRY
1-2 SEC
IBC 
CHECKS 
N.O. AIR
PRESSURE
SWITCH
CONTACTS
FALSE 
POSITIVE 
PROOF OF 
AIRFLOW. IBC WAITS 
FOR 45 SEC 
FOR AIR PRESSURE 
SWITCH CONTACTS 
TO OPEN
CLOSED
CLOSED
DRAFT INDUCER
ENERGIZES THRU
1K1 CONTACTS
OPEN
IBC 
WAITS FOR 
UP TO  5 MINUTES 
FOR AIR PRESSURE 
SWITCH CONTACTS TO CLOSE
INDICATING FAN 
SUCTION 
PRESENT
CLOSED
CONTROL LOCKOUT. 
PURGE LIGHT 
BLINKS. RESET REQUIRED.  CIRCULATOR 
REMAINS ENERGIZED AS LONG AS 
THERMOSTAT CONTINURES TO CALL FOR 
HEAT
OPEN
PURGE LIGHT IS ON.  
   AIRFLOW PROVED.
DRAFT INDUCER RUNS FOR 15 SEC PREPURGE
OPEN
PURGE LIGHT GOES OUT. HOT SURFACE IGNITER 
POWERED THRU 5K1 5K2 CONTACTS FOR 20 
SEC IGNITER WARMUP. BRIGHT YELLOW 
ORANGE GLOW OF THE HOT SURFACE IGNITER 
CAN BE OBSERVED THRU THE OBSERVATION 
PORT IN FRONT OF BOILER SECTION JUST 
ABOVE IGNITER,
  IGNITOR LIGHT IS ON
GAS VALVE ENERGIZED THRU 3K1 AND 4K1.
CONTACTS, 
 VALVE LIGHT IS ON.
GAS VALVE OPENS FOR 5 SEC TRIAL FOR 
IGNITION. BLUE ORANGE GLOW OF THE BURNER 
CAN BE SEEN THRU OBSERVATION PORT.
2 SEC INTO THE 5 SEC IGNITION TRIAL. POWER 
IS TURNED OFF TO THE HOT SURFACE IGNITER. 
IGNITER LIGHT IS OFF.
DURING THE LAST 2 SEC OF THE 5 SEC IGNITION 
TRIAL MAIN BURNER FLAME IS PROVED BY FLAME 
RECTIFICATION A  FLAME SIGNAL TO IBC. GAS VALVE 
REMAINS ENERGIZED. BOILER RUNS.
DOES 
MAIN 
BURNER PROVE 
FLAME WITHIN INITIAL 
TRIAL FOR 
IGNITION 
PERIOD?
CONTROL WILL ATTEMPT 2 
ADDITTIONAL IGNITION SEQUENCES.
STARTING WITH PREPURGE.
IF MAIN BURNER DOES NOT PROVE 
FLAME IN 3 TRIALS, CONTROL 
LOCKOUT. 
VALVE/FLAME LIGHT BLINKS
RESET IS REQUIRED. THIS PROBLEM IS A 
RESULT OF NOT ESTABLISHING FLAME SIGNAL.
NORMAL 
OPERATION
YES
NO
12 - DETAILED SEQUENCE OF OPERATION