BMC Heat Pump GTA3600UD1AA User Manual

Page of 54
Manual 2100-537
I
  
Page 
5 of 54
TABLE  1 — INDOOR BLOWER PERFORMANCE  (RATED CFM)  
 Motor will automatically step through the various airflows with thermostatic control
  ESP = External Static Pressure (inches of water)
Maximum allowable duct static
 Continuous airflow is the CFM being circulated with manual fan operation without any additional function occurring.
 Will occur automatically for first 5 minutes of Part Load Cooling Operation.
 Will occur automatically after five minutes of Part Load Cooling Operation.
  Will occur automatically with control signal input.
  As per ASHRAE Guidelines of 500 FPM Velocities.
MODEL
Rated
ESP
MAX
ESP
Continuous
Airflow
Mild Climate 
Operation 
in Part Load 
Cooling
Part Load 
Airflow
Full Load 
Airflow
Electric Heat 
Airflow
Minimum Air 
Filter Face 
Area Ft.2
GTC36S2
0.15
0.60
600
700
850
1200
1300
2.6
GTC48S2
0.20
0.60
750
875
1075
1500
1600
3.2
GTC60S2
0.20
0.60
900
1050
1300
1800
1800
3.6
APPLICATION
MODELS
GTC36S2
GTC48S2
GTC60S2
Ground Loop (15% Methanol, Propylene Glycol, etc.)
8
12
15
Ground Water
6
7
9
Water Loop (Cooling Tower)
9.2
12.1
14.3
MODEL
GTC36S2
GTC48S2
GTC60S2
Electrical Rating (60HZ/1PH)
230/208-60-1
Operating Voltage Range
253-197 VAC
Minimum Circuit Ampacity 
24.5
33.1
39.7
+Field Wire Size
#10
#6
#4
Ground Wire Size
#10
#10
#10
++Delay Fuse or Circuit Breaker Max.
35
50
60
COMPRESSOR
Volts
230/208-60-1
Rated Load Amps (230/208)
10.6 / 11.9
15.3 / 17.0
20.2 / 22.7
Branch Circuit Selection Current
15.3
21.2
25.6
Locked Rotor Amps (230/208)
82 / 82
104 / 104
153 / 153
BLOWER MOTOR
Horsepower (ECM Motor)
3/4 Variable Speed
Volts
230/208-60-1
Motor Amps (Stage #2 @ Rated CFM)
3.4
4.3
4.4
FLOW CENTER (Based on DORFC-2)
Volts
230/208-60-1
Amps
2.14
2.14
2.14
DESUPERHEATER PUMP MOTOR
Volts
230/208-60-1
Amps
0.15
0.15
0.15
TABLE  2 — FLOW RATES FOR VARIOUS FLUIDS
TABLE  3 — SPECIFICATIONS
+75°C copper wire      ++ HACR type circuit breaker
NOTE: 
All values can be changed + 10% via the + adjustment dip switches on the tap select control inclusive in the GTB1-A Blower Section  
 
(see instructions later in this manual, or on wiring diagram in blower section).