TROUBLESHOOTING  GE  ECM
 MOTORS CONT’D.
10
1
2 3
4
5
6
7
8
16
15
14
13
12
11
9
3
5
1 2
4
MIS-2839
FIGURE  25
CONTROL CONNECTOR MOTOR HALF
*  Suggested mating connector
 
Housing — AMP 350809-1
 
Contact — AMP 350537-1
**  WARNING — Applying 240VAC line input with  
 
PIN 1 to PIN 2 jumper in place will permanently  
 
damage unit!
POWER CONNECTOR 
MOTOR HALF
MODE of 
OPERATION
OFF Continuous 
Blower
Part Load 
Cooling
Full Load Cooling
Part 
Load 
Heating
Full Load 
Heating
Full Load Heating + 
Electric Heat
Stage #1
Emergency Heat 
Mode
Thermostat 
24 VAC Inuput 
Signals
"G"
"G", "Y1", "O" "G", "Y1", "Y2", "O" "G", "Y1" "G", "Y1", "Y2"
"G", "Y1", "Y2", "W1"
"G", "E", "W1", "W2"
Pin #1
24 VAC "C" (Common) Signal, Always Energized
Pin #2
X
X
Pin #3
24 VAC "C" (Common) Signal, Always Energized
Pin #4
Delay Tap Profiles, Varied Half-Wave Signals Based Upon Settings
Pin #5
Cool Tap Select Tables, Varied Half-Wave Signals Based Upon Settings (Tonnage)
Pin #6
X
X
X
X
X
Pin #7
Adjustment Tap Profiles, Varied Half-Wave Signals Based Upon Settings
Pin #8
DC Volts "-" Output in Direct Correlation to CFM
Pin #9
X
X
Pin #10
Future Use; Not Currently Programmed for Function
Pin #11
Heat Tap Select Tables, Varied Half-Wave Signals Based Upon Tonnage
Pin #12
24 VAC Hot "R" Signal, Always Energized
Pin #13
X
Pin #14
X
X
Pin #15
X
X
X
X
X
X
X
Pin #16
DC Volts "+" Output in Direct Correlation to CFM
POWER CONNECTOR  *
PWB HEADER
AMP 1-350945-0
PIN
Description
1
Jumper Pin 1 to Pin 2 for 
120VAC Line Input Only **
2
3
Chassis Ground
4
AC Line
5
AC Line