HP Performance Optimized Data Center (POD) 40c Quick Setup Guide

Page of 41
 
Site plan requirements and actions  25 
 
Assembly equipment locations 
 
HP POD 40c G2 lifting requirements 
  
 
WARNING:
  The only approved method for lifting the HP POD 40c G2 is the use of a spreader 
bar harness. Lifting an HP POD 40c G2 in any other manner can cause damage to the HP POD 
40c G2 and void your warranty. 
  
 
HP POD 40c G2 storage requirements 
If the site is not ready for assembly and operation, determine a location for storage when creating the site 
plan. 
  
 
CAUTION: 
 The HP POD 40c G2 must maintain 20% relative humidity to minimize condensation 
and oxidation within the HP POD 40c G2. 
  
  
 
CAUTION: 
 While being stored, the HP POD 40c G2 must be kept in a level position even if 
stored on a trailer. 
  
Changes in ambient temperatures can cause condensation in a non-operational HP POD 40c G2. If the HP 
POD 40c G2 is placed in storage or is in non-operating mode for over 72 hours, HP recommends using one 
of the following methods to minimize condensation and oxidation within the HP POD 40c G2: 
 
Desiccant unit 
 
Desiccant material 
 
Heater with a fan 
 
Air conditioner with a heater strip 
Consult with HP Services to determine the most effective method. 
 
Additional structures 
If a customer-provided vestibule or other structure is installed and connected to the HP POD 40c G2, the 
following specifications must be maintained: 
 
To protect the HP POD 40c G2 and ensure a waterproof barrier, flashing must be installed to the 
exterior of the HP POD 40c G2 in the location where the other structure is attached.