HP Performance Optimized Data Center (POD) 40c Service Manual

Page of 82
 
Removal and replacement procedures  36 
Removing the external chilled water flow valve 
1. 
Remove the external chilled water flow actuator. For detailed instructions, see "Removing the external 
chilled water flow actuator (on page 
)." 
2. 
Remove the eight bolts surrounding the valve (1), and then remove the valve (2). 
 
 
Replacing the external chilled water flow valve 
1. 
Replace the valve (1), and then secure the valve with eight bolts (2). 
 
2. 
Replace the external chilled water flow actuator. For detailed instructions, see "Replacing the external 
chilled water flow actuator (on page 
)."