Kidde Fire Systems Marine Instruments FM-200 Leaflet

Page of 1
A UTC Fire & Security Company
This literature is provided for informational purposes only.  KIDDE-FENWAL, INC. assumes 
no responsibility for the product’s suitability for a particular application.  The product must be 
properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question, 
contact KIDDE-FENWAL, INC., Ashland, MA 01721.  Telephone: (508) 881-2000.
Kidde Fire Systems
A UTC Fire & Security Company
400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com
K-90-5180  Rev AC
© 2010 Kidde-Fenwal Inc.
Printed in USA
Effective:  September 2010
K-90-5180
FM-200
®
 Component Description
Pressure Operated Switch
FEATURES
For Use with UL Listed, ULC Listed and
FM Approved Systems
See Kidde
®
 Manual 90-FM200M-021 for
USCG Approval
P/N:
81-486536-000
OPERATED
SET
4.00"
WIRING
SCREW
TERMINALS
4.00"
SET
OPERATED
PRESSURE OPERATED SWITCH
3P.D.T.
UL
TO RESET
PUSH STEM TO SET POSITION
15 AMP 125 VAC
10 AMP 250 VAC
3/4 HP 1-2-3 PH 125-480 VAC
8 COVER SCREWS
STEM SHOWN IN SET POSITION-
PULL UP ON STEM TO MANUALLY
OPERATE SWITCH
0.375"
1/2” SUPPLY PIPE WITH UNION
FRONT VIEW
FRONT VIEW
COVER REMOVED
SWITCH 3PDT
COVER
GASKET
BOX 3 EACH SIDE
1/2” CONDUIT
KNOCKOUTS
½” NPT FEMALE,
CONNECT TO SYSTEM
PIPING
SIDE SECTION
TO RESET
PUSH STEM TO SET POSITION
FM
15 AMP.— 125 V.AC           10 AMP.—250 V.AC
3/4HP—250 VAC
PT. NO. 486536
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
WIRING DIAGRAM
SET
OPERATED
PRESSURE INLET
C
NC
NO
C
NC
NO
C
NC
NO
FM-200 is a registered trademark of the Great Lakes Chemical Corporation.
NOTES:
The switch may be mounted in any position; how-
ever, the preferred installation is upright, as shown.
Any load connection to the switch must not exceed 
the switch rating, and shall utilize a suitable protec-
tion device (i.e., circuit breaker, fuse).
Contact Ratings (3 PDT):
15 Amp @125 Vac
10 Amp @ 250 Vac
3/4 HP @ 250 Vac
1, 2 or 3 Phase